• Indoor Units • Wall Mounted Unit • FXAQ-MAVE9• VRV ® Systems • Indoor Units21 Specifications1VRV®Systems IndoorUnit FXAQ-MAVE9 WallMounte1-1 TECHNICAL SPECIFICATIONS FXAQ20MAVE9 FXAQ25MAVE9 FXAQ32MAVE9 FXAQ40MAVE9 FXAQ50MAVE9 FXAQ63MAVE9Capacity Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1Heating kW 2.5 3.2 4.0 5.0 6.3 8.0Power Input (50Hz) Cooling kW 0.016 0.022 0.027 0.020 0.027 0.050Heating kW 0.024 0.027 0.032 0.020 0.032 0.060Power Input (60Hz) Cooling kW 0.016 0.022 0.027 0.020 0.027 0.050Heating kW 0.024 0.027 0.032 0.020 0.032 0.060Casing Colour white (3.0Y8.5/0.5)Dimensions Unit Height mm 290Width mm 795 795 795 1,050 1,050 1,050Depth mm 230Weight Unit kg 11 11 11 14 14 14Heat Exchanger Dimensions Nr of Rows 2Fin Pitch mm 1.40Face Area m² 0.161 0.161 0.161 0.213 0.213 0.213Nr of Stages 14Fan Type Cross flow fanQuantity 1Cooling High m³/min 7.5 8 9 12 15 19Low m³/min 4.5 5 5.5 9 12 14Fan Motor Quantity 1Model QCL9661M QCL9661M QCL9661M QCL9686M QCL9686M QCL9686MOutput (high) W 40 40 40 43 43 43Drive Direct driveRefrigerant Name R-410ACooling Sound Pressure High dBA 35.0 36.0 37.0 39.0 42.0 46.0Low dBA 29.0 29.0 29.0 34.0 36.0 39.0Piping connections Liquid (OD) Type Flare connectionDiameter mm 6.35 6.35 6.35 6.35 6.35 9.52Gas Type Flare connectionDiameter mm 12.7 12.7 12.7 12.7 12.7 15.9Drain Diameter mm VP13 (I.D. 13/O.D. 18)Heat Insulation Foamed polystyrene/foamed polyethyleneAir Filter Washable resin netRefrigerant control Electronic expansion valveTemperature control Microprocessor thermostat for cooling and heatingSafety devices PC board fuseStandard Accessories Installation and operation manualInstallation panelPaper pattern for installationInsulation tapeClampsScrewsNotes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping : 5m (horizontal)Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,6°CWB, equivalent refrigerant piping : 5m (horizontal)Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.