EDUS391100-F6 SpecificationsFXAQ-PVJU 3Wall Mounted TypeNotes: 1 Nominal cooling capacities are based on the following conditions:Return air temperature: 80°FDB, 67°FWB (27°CDB /19.4°CWB)Outdoor temperature: 95°FDB (35°CDB)Equivalent ref. piping length: 25ft (7.5 m) (Horizontal) 2 Nominal heating capacities are based on the following conditions:Return air temperature: 70°FDB (21°CDB).Outdoor temperature: 47°FDB, 43°FWB (8.3°CDB / 6°CWB)Equivalent ref. piping length: 25ft (7.5 m) (Horizontal) 3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 4 Sound levels are measured under JIS conditions.5 Refer to page 9 for Power Input.Model FXAQ18PVJU FXAQ24PVJUPower Supply 1 phase, 208/230V, 60Hz1, 3 Cooling Capacity Btu/h 18,000 24,0002, 3 Heating Capacity Btu/h 20,000 26,500Casing Color White (3.0Y8.5/0.5) White (3.0Y8.5/0.5)Dimensions: (H×W×D) in (mm) 11–3/8 × 41–3/8 × 9–1/4(289 x 1051 x 235)11–3/8 × 41–3/8 × 9–1/4(289 x 1051 x 235)Coil (CrossFin Coil)Rows×Stages×FPI 2×14×17 2×14×17Face Area ft² (m²) 2.29 (0.7) 2.29 (0.7)FanModel QCL9686M QCL9686MType Cross Flow Fan Cross Flow FanMotor Output W 43 43Air Flow Rate (H/L) cfm (m 3 /min) 500/400 (152/122) 635/470 (194/143)Drive Direct Drive Direct DriveTemperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and HeatingSound Absorbing Thermal Insulation Material Foamed Polystyrene /Foamed Polyethylene Foamed Polystyrene /Foamed PolyethyleneAir Filter Resin Net (Washable) Resin Net (Washable)Machine Weight (Mass) Lbs (kg) 31 (14) 31 (14)PipingConnectionsLiquid Pipes in (mm) 1/4 (6.4) (Flare Connection) 3/8 (9.5) (Flare Connection)Gas Pipes in (mm) 1/2 (12.7) (Flare Connection) 5/8 (15.8) (Flare Connection)Drain Pipe in (mm) VP13(External Dia. 11/16 (17.5) Internal Dia. 1/2 (12.7))VP13(External Dia. 11/16 (17.5) Internal Dia. 1/2 (12.7))4 Sound Level (H/L) dB(A) 43/37 47/41Safety Devices Fuse FuseRefrigerant Control Electronic Expansion Valve Electronic Expansion ValveConnectable outdoor unit R-410A VRV Series R-410A VRV SeriesStandard AccessoriesOperation Manual, Installation Manual, Installation Panel,Paper Pattern for Installation, Insulation tape, InsulationTube, Clamps, Screws.Operation Manual, Installation Manual, Installation Panel,Paper Pattern for Installation, Insulation tape, InsulationTube, Clamps, Screws.Drawing No. C: 3D075572A