14CAUTION• Drain piping connectionsDo not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in thesewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.7. ELECTRIC WIRING WORK7-1 GENERAL INSTRUCTIONS• All field supplied parts and materials and electric works must conform to local codes.• Use copper wire only.• For electric wiring work, refer to also “WIRING DIAGRAM” attached to the unit.• For remote controller wiring details, refer to the installation manual attached to the remote controller.• All wiring must be performed by an authorized electrician.• This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure theterminal block wiring to the outdoor unit and BS unit is properly matched. If wiring and piping between theoutdoor unit and indoor unit are mismatched, the system may cause a malfunction.• A circuit breaker capable of shutting down power supply to the entire system must be installed.• Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connectedto the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.• Be sure to ground the air conditioner.DANGER• Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding couldcause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak couldresult in an explosion which could lead to severe injury or death.7-2 ELECTRICAL CHARACTERISTICSMCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)W: Fan Motor Rated Output (W); FLA: Full Load Amps (A)7-3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE• Allowable length of transmission wiring and remote controller wiring are as follows.(1) Outdoor unit - Indoor unit:Max.3280ft. (Total wiring length: 6560ft.)(2) Indoor unit - Remote controller:Max.1640ft.• Insulated thickness: 1/16” or more.Units Power supply Fan motorModel Hz Volts Voltage range MCA MFA W FLAFXAQ07MVJU60 208-230 Max. 253Min. 1870.3 15 40 0.2FXAQ09MVJU 0.3 15 40 0.2FXAQ12MVJU 0.4 15 40 0.3FXAQ18MVJU 0.4 15 43 0.3FXAQ24MVJU 0.6 15 43 0.5Model Power supply wiring Remote controller wiringTransmission wiringField fuses Size Wire SizeFXAQ07MVJU15ASize mustcomply withlocal codes.Sheathed wire (2 wire) AWG18-16FXAQ09MVJUFXAQ12MVJUFXAQ18MVJUFXAQ24MVJU