16 EnglishUse a round crimp-style terminal for connection to the power supply terminal block. In case it cannot be useddue to unavoidable reasons, be sure to observe the following instructions.Be sure to peel off the sheath of power supply wiring more than 40 mm. (Refer to Fig. 20)• For remote controller wiring, refer to the “INSTALLATION MANUAL OF REMOTE CONTROLLER.”attached to the remote controller.• Never connect power supply wiring to the terminal block for remote controller. A mistake of the sortcould damage the entire system.• Use only specified wire and tightly connect wires to terminals. Be careful wires do not place external stresson terminals. Keep wiring in neat order and so as not to obstruct other equipment such as popping open thecontrol box cover. Make sure the cover closes tight. Incomplete connections could result in overheating,and in worse case, electric shock or fire.CAUTION• Be sure to attach the sealing material and putty (field supplied) to hole of wiring to prevent the infiltration ofwater as well as any insects and other small creatures from outside. Otherwise a short-circuit may occurinside the control box.Round crimp-style terminalAttach insulation sleevePower supply wiring and earth wire40mmor moreFig. 20REMOTECNTRL FORCEDOFFTRANSMISSIONWIRINGF1 F2 T1 T2P1 P2L NTerminal block (6P)Earth terminalEarth wiringPower supply wiringPower supplyterminal block (3P)In case of using the powersupply terminal together withthe other connecting wiringsMake sure to processthe insulation at the wireterminal part properly so thatthe terminals do not get incontact each other.Fig. 21Remotecontroller wiringL NEarth wiringPower supply wiringTransmission wiringTransmissionwiring< Wiring clamp method >Clamp small(accessory) (5)Clamp small(accessory) (5)Clamp small(accessory) (5)Clamp after tying thewiring between the unitsand the earth wiring.Remote controllerwiring(3 places)Cut off any excessmaterial after tightening.