14 English7-2 ELECTRICAL CHARACTERISTICSMCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)7-3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIREAllowable length of transmission wirings and remote controller wiring are as follows.(1) Outdoor unit - Indoor unit: Max. 1000m (Max. wiring length: 2000m)(2) Indoor unit - Remote controller: Max. 500mNOTE1. Shows only in case of protected pipes. Use H07RN-F in case of no protection.2. Vinyl cord with sheath or cable (Insulated thickness : 1mm or more)CAUTION• Arrange the wires and fix a cover firmly so that the cover does not float during wiring work.• Do not clamp remote controller wiring and transmission wiring together with power supply wiring. Doing somay cause malfunction.• Remote controller wiring and transmission wiring should be located at least 50 mm from power supply wir-ing. Not following this guideline may result in malfunction due to electrical noise.8. HOW TO CONNECT WIRINGS AND WIRING EXAMPLE8-1 HOW TO CONNECT WIRINGSMethods of wiring power supply, units and connecting remote controller wiring• Power supply wiring and earth wireUnscrew and remove the service cover.Connect the power supply wiring and earth wiring to the power supply terminal block (3P).When doing this, tie the power supply wiring and the earth wiring using the included clamp (small) (5) andthen firmly secure using the included clamp (small) (5) according to the figure.(Refer to Fig. 23)Units Power supply Fan motorModel Hz Volts Voltage range MCA MFA kW FLAFXAQ20PVE50 220 - 240 Max. 264Min. 1980.3 15 0.040 0.2FXAQ25PVE 0.4 15 0.040 0.3FXAQ32PVE 0.4 15 0.040 0.3FXAQ40PVE 0.4 15 0.043 0.3FXAQ50PVE 0.5 15 0.043 0.4FXAQ63PVE 0.6 15 0.043 0.5FXAQ20PVE60 220 Max. 242Min. 1980.3 15 0.040 0.2FXAQ25PVE 0.4 15 0.040 0.3FXAQ32PVE 0.4 15 0.040 0.3FXAQ40PVE 0.4 15 0.043 0.3FXAQ50PVE 0.5 15 0.043 0.4FXAQ63PVE 0.6 15 0.043 0.5ModelPower supply wiring Remote controller wiringTransmission wiringField fuses Wire Size Wire SizeFXAQ20PVE15A H05VV - U3GNOTE 1)Wire size andlength mustcomply withlocal codes.Vinyl cord withsheath or cable(2 wire)NOTE 2)0.75 - 1.25 mm 2FXAQ25PVEFXAQ32PVEFXAQ40PVEFXAQ50PVEFXAQ63PVE