• Indoor Unit • 2-way blow ceiling mounted cassette • FXCQ-A16• VRV Systems • Indoor Unit106 Capacity tables6 - 3 Capacity Correction FactorIndoor airtemperature14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDBFXCQ20 TC 0.667 0.697 0.748 0.767 0.788 0.817 0.844SHF 1.172 1.184 1.130 1.106 1.084 1.061 1.039FXCQ25 TC 0.681 0.690 0.741 0.766 0.787 0.817 0.842SHF 1.147 1.192 1.135 1.108 1.086 1.061 1.041FXCQ32 TC 0.681 0.690 0.741 0.766 0.787 0.817 0.842SHF 1.147 1.192 1.135 1.108 1.086 1.061 1.041FXCQ40 TC 0.671 0.687 0.748 0.772 0.792 0.821 0.854SHF 1.167 1.191 1.128 1.101 1.082 1.059 1.035FXCQ50 TC 0.663 0.690 0.753 0.777 0.795 0.831 0.857SHF 1.177 1.185 1.123 1.097 1.081 1.054 1.034FXCQ63 TC 0.682 0.692 0.740 0.763 0.784 0.815 0.840SHF 1.144 1.191 1.138 1.111 1.088 1.061 1.042FXCQ80 TC 0.707 0.689 0.752 0.776 0.795 0.830 0.856SHF 1.166 1.187 1.124 1.098 1.080 1.055 1.035FXCQ125 TC 0.683 0.691 0.753 0.776 0.796 0.831 0.855SHF 1.132 1.180 1.121 1.096 1.077 1.054 1.043FXCQ-A3D079901Capacity correction factor Te = 9°C