FXCQ20~125M8V3BVRV System air conditioners4PW25081-1AInstallation and operation manual4Precautions■ Instal the drain raising pipes at a height of less than 310 mm.■ Install the drain raising pipes at a right angle to the indoor unitand no more than 300 mm from the unit.2. After piping work is finished, check if drainage flows smoothly.• Open the water inlet lid, add approximately 2 l of water graduallyand check the drainage flow.Method of adding water. See figure 10.If adding water from the charge inlet at the fan casing, be sure to putthe lid back in its original position.When electric wiring work is finishedCheck drainage flow during COOL running, explained in chapter"Test operation" on page 7.When electric wiring work is not finished■ Remove the switch box lid and connect the power supply andremote controller to the terminals.See figure 11.• Next, press the inspection/test operation button on theremote controller. The unit will engage the test operation mode.Press the operation mode selector button until selecting fanoperation . Then, press the on/off button . The indoor unitfan and drain pump will start up. Check that the water has drainedfrom the unit. Press to go back to the first mode.Electric wiring workGeneral instructions■ All field supplied parts and materials and electric works mustconform to local codes.■ Use copper wire only.■ Follow the "Wiring diagram" attached to the unit body to wire theoutdoor unit, indoor units and the remote controller. For detailson hooking up the remote controller, refer to the "Installationmanual of the remote controller".■ All wiring must be performed by an authorized electrician.■ A circuit breaker capable of shutting down power supply to theentire system must be installed.■ This system consists of multiple indoor units. Mark each indoorunit as unit A, unit B..., and be sure the terminal board wiring tothe outdoor unit and BS unit are properly matched. If wiring andpiping between the outdoor unit and an indoor unit aremismatched, the system may cause a malfunction.Electrical characteristicsMCA: Min. circuit Amps (A)MFA: Max. Fuse Amps (A)kW: Fan Motor Rated Output (kW)FLA: Full Load Amps (A)Specifications for field supplied fuses and wireNOTE ■ The incline of attached drain hose should be75 mm or less so that the drain socket does nothave to stand additional force.■ To ensure a downward slope of 1:100, installhanging bars every 1 to 1.5 m.■ If unifying multiple drain pipes, install the pipes asshown in figure 9. Select converging drain pipeswhose gauge is suitable for the operating capacityof the unit.1 T-joint converging drain pipes1 Portable pump2 Water inlet lid3 Close4 Open5 Bucket6 Refrigerant piping7 Water inlet1 Clamps A and B details2 Clip3 Terminal board4 220 V-240 V single phase power supply5 Electric parts box6 Terminal board for transmission wiring7 Clamp B8 Transmission wiring9 Guide plate10 Power supply wiring11 Clamp A12 Terminal board for power supply13 Electric parts box lidTESTTESTModel Hz Volts Voltage rangeFXCQ20~125 50 230 min.198-max.264Power supply Fan motorModel MCA MFA kW FLAFXCQ20 0.5 16 A 0.010 0.4FXCQ25+32 0.5 16 A 0.015 0.4FXCQ40+50 0.8 16 A 0.020 0.6FXCQ63 0.9 16 A 0.030 0.7FXCQ80 1.1 16 A 0.050 0.9FXCQ125 1.3 16 A 0.085 1.0NOTE For details, refer to "Electrical data".Power supply wiringModel Field fuses Wire SizeFXCQ20~125 16 A H05VV-U3G Local codesTransmission wiringModel Wire SizeFXCQ20~125 Sheathed wire (2) 0.75-1.25mm2NOTE ■ For details, refer to the chapter "Wiring example"on page 5.■ Allowable length of transmission wiring betweenindoor and outdoor units, and between the indoorunit and the remote controller is as follows:• Outdoor unit - indoor unit: max. 1000 m(total wiring length: 2000 m)• Indoor unit - remote controller: max 500 m