ï Indoor Units ï 2-Way Blow Ceiling Mounted Cassette ï FXCQ-MVE911ï VRV Æ Systems ï Indoor Units41 SpecificationsNotes Nominal cooling capacities are based on : indoor temperature : 27∞CDB, 19∞CWB, outdoor temperature: 35∞CDB, equivalent refrigerant piping : 7.5m (horizontal)Nominal heating capacities are based on : indoor temperature : 20∞CDB, outdoor temperature : 7∞CDB,6∞CWB, equivalent refrigerant piping : 7.5m (horizontal)Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.1-2 ELECTRICAL SPECIFICATIONS (50HZ) FXCQ20MVE9 FXCQ25MVE9 FXCQ32MVE9 FXCQ40MVE9 FXCQ50MVE9 FXCQ63MVE9 FXCQ80MVE9 FXCQ125MVE9Power Supply Name VEPhase 1~Frequency Hz 50Voltage V 220-240Current Minimum circuit amps (MCA) A 0.5 0.5 0.5 0.8 0.8 0.9 1.1 1.3Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15Full load amps (FLA) A 0.4 0.4 0.4 0.6 0.6 0.7 0.9 1.0Voltage range Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminalsis not below or above listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 x FLAMFA is smaller than or equal to 4 x FLANext lower standard fuse rating minimum 15ASelect wire size based on the MCAInstead of a fuse, use a circuit breaker1-3 ELECTRICAL SPECIFICATIONS (60HZ) FXCQ20MVE9 FXCQ25MVE9 FXCQ32MVE9 FXCQ40MVE9 FXCQ50MVE9 FXCQ63MVE9 FXCQ80MVE9 FXCQ125MVE9Power Supply Name VEPhase 1~Frequency Hz 60Voltage V 220Current Minimum circuit amps (MCA) A 0.5 0.5 0.5 0.8 0.8 0.9 1.3 1.5Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15Full load amps (FLA) A 0.4 0.4 0.4 0.6 0.6 0.7 1.0 1.2Voltage range Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminalsis not below or above listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 x FLAMFA is smaller than or equal to 4 x FLANext lower standard fuse rating minimum 15ASelect wire size based on the MCAInstead of a fuse, use a circuit breaker1-1 TECHNICAL SPECIFICATIONS FXCQ20MVE9 FXCQ25MVE9 FXCQ32MVE9 FXCQ40MVE9 FXCQ50MVE9 FXCQ63MVE9 FXCQ80MVE9 FXCQ125MVE9