Installation and operation manual2AccessoriesCheck if the following accessories are included with your unit.Optional accessories There are two types of remote controllers: wired andwireless. Select a remote controller according to customersrequest and install in an appropriate place.Refer to catalogues and technical literature for selecting asuitable remote controller. This indoor unit requires installation of an optional decorationpanel.For the following items, take special care duringconstruction and check after installation is finishedSelecting installation siteWhen the conditions in the ceiling are exceeding 30°C and arelative humidity of 80%, or when fresh air is inducted into theceiling, an additional insulation is required (minimum 10 mmthickness, polyethylene foam).For this unit you can select different air flow directions. It isnecessary to purchase an optional blocking pad kit to dischargethe air in 3 or 4 (closed corners) directions.Install the unit so that air vents, lights, or machines near the unitdo not interfere with the air flow.1 Metal clamp2 Drain hose3 Washer for hanger bracket4 Screw5 Installation guide6 Installation and operation manual7 Insulation for fitting for gas pipe8 Insulation for fitting for liquid pipe9 Large sealing pad10 Medium 1 sealing pad11 Medium 2 sealing pad12 Small sealing pad13 Drain sealing pad14 Paper pattern for installation (upper part of packing)15 ClampInformation requirements for fan coil unitsItem Symbol Value UnitCooling capacity(sensible) Prated, c A kWCooling capacity (latent) Prated, c B kWHeating capacity P rated, h C kWTotal electric power input P elec D kWSound power level(per speed settingif applicable)LWA E dBContact details DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o.U Nové Hospody 1/1155, 301 00 PlzeňSkvrňany, Czech RepublicTHE ABOVE TABLE RELATES TO THE MODELSAND VALUES STATED IN THIS TABLEModels A B C D EFXFQ20AVEB 1.8 0.4 2.5 0.038 49FXFQ25AVEB 2.1 0.7 3.2 0.038 49FXFQ32AVEB 2.8 0.8 4 0.038 49FXFQ40AVEB 3.4 1.1 5 0.038 51FXFQ50AVEB 4.1 1.5 6.3 0.053 51FXFQ63AVEB 5.2 1.9 8 0.061 53FXFQ80AVEB 6.5 2.5 10 0.092 55FXFQ100AVEB 7.8 3.4 12.5 0.115 60FXFQ125AVEB 9.8 4.2 16 0.186 611x 1x 8x 4x 1x 1x 1x1x 1x 1x1x1x 1x 1x 7x1 2 3 54 6 78 9 11 1210 13 14 15Tick whenchecked Is the indoor unit fixed firmly?The unit may drop, vibrate or make noise. Is the gas leak test finished?It may result in insufficient cooling or heating. Is the unit fully insulated?Condensate water may drip. Does drainage flow smoothly?Condensate water may drip. Does the power supply voltage correspond to that shown on thename plate?The unit may malfunction or components may burn out. Are wiring and piping correct?The unit may malfunction or components may burn out. Is the unit safely grounded?Dangerous at electric leakage. Is the wiring size according to specifications?The unit may malfunction or components may burn out. Is nothing blocking the air outlet or inlet of either the indoor oroutdoor units?It may result in insufficient cooling or heating. Are refrigerant piping length and additional refrigerant chargenoted down?The refrigerant charge in the system might not be clear.(1) GWP = global warming potentialPeriodical inspections for refrigerant leaks may berequired depending on European or local legislation.Please contact your local dealer for more information.Important information regardingthe refrigerant usedThis product contains fluorinated greenhouse gases.Do not vent gases into the atmosphere.Refrigerant type:GWP (1) value: 2087.5R410ANOTICE regarding tCO 2 eqIn Europe, the greenhouse gas emissions ofthe total refrigerant charge in the system(expressed as tonnes CO 2 -equivalent) is usedto determine the maintenance intervals. Followthe applicable legislation.Formula to calculate the greenhouse gasemissions:GWP value of the refrigerant × Total refrigerantcharge [in kg] / 1000