English 1110. DECORATION PANEL INSTALLATIONRefer to the installation manual of the panels.[ PRECAUTIONS ]• SWING FLAP MOTOR WIRING METHOD(1) CONNECT TWO LEAD WIRES OF SWING FLAP MOTORMOUNTED ON THE DECORATION PANEL TO THE CON-NECTORS OF MAIN BODY.(2) SLIDE THE INSULATION TUBE ACCORDING TO THEARROW AS SHOWN IN FIG. SO THAT THE CONNEC-TOR CAN BE COMPLETELY COVERED.(3) BIND THE OPENING OF INSULATION TUBE WITH THEATTACHED CLAMP MATERIAL.11. FIELD SETTINGMake sure the terminal box lids are closed on the indoorand outdoor units.Field setting must be made from the remote controller inaccordance with the installation condition.• Setting can be made by changing the “Mode No.”, “FIRSTCODE NO.”, and “SECOND CODE NO.”.• For setting and operation, refer to the “FIELD SETTING” inthe installation manual of the remote controller.• Set the remote controller to the field set mode.For details, refer to the “HOW TO SET IN THE FIELD”, inthe remote controller manual.• When in the field set mode, select mode No. 12, then setthe first code (switch) No. to “1”. Then set second code(position) No. to “01” for FORCED OFF and “02” for ON/OFF OPERATION. (FORCED OFF at factory set)12. TEST OPERATIONRefer to the installation manual of the outdoor unit.• The operation lamp of the remote controller will flash whenan malfunction occurs. Check the malfunction code on theliquid crystal display to identify the point of trouble. An expla-nation of malfunction codes and the corresponding trouble isprovided in “CAUTION FOR SERVICING” of the indoor unit.If any of the items in Table 5 are displayed, there may be aproblem with the wiring or power, so check the wiring again.Table 5CLAMP MATERIAL(accessory)SETTINGMode No.SECONDCODE NO.FIRST CODENO. FIELD SETMODERemote control display Content“Concentrated Manage-ment” is lit up• There is a short circuit at theFORCED OFF terminals (T1, T2).“U4” is lit up“UH” is lit up• The power on the outdoor unit is off.• The outdoor unit has not been wiredfor power supply.• Incorrect wiring for the transmissionwiring and / or FORCED OFF wiring.No display• The power on the indoor unit is off.• The indoor unit has not been wired forpower supply.• Incorrect wiring for the remote control-ler wiring, the transmission wiring,and / or the FORCED OFF wiring.