Capacity Tables EDUS391502-F718 FXLQ-M / FXNQ-M8. Capacity Tables8.1 Cooling Capacity at Te: 43°F (6°C)TC: Total capacity: MBHSHC: Sensible heat capacity: MBHNotes: 1. These capacity tables can be used when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors suchas the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRVsystem satisfies the required heat load.2. shows rated condition.8.2 Heating CapacityTC: Total capacity: MBHNotes: 1. These capacity tables can be used when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors suchas the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRVsystem satisfies the required heat load.2. shows rated condition.8.3 Correction Factor for Cooling Capacity at Te: 48°F (9°C)TC: Total capacitySHF: Sensible heat factorModelIndoor air temp. °FWB (Te: 43°F (6°C))61 64 67 70 72 75TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBHFXLQ07MVJUFXNQ07MVJU 5.9 4.9 6.7 5.4 7.5 5.8 7.6 5.6 7.7 5.1 7.9 4.8FXLQ09MVJUFXNQ09MVJU 7.5 5.9 8.5 6.5 9.5 7.1 9.7 6.9 9.8 6.4 10.0 6.0FXLQ12MVJUFXNQ12MVJU 9.5 7.5 10.7 7.9 12.0 8.3 12.7 8.4 12.9 8.0 13.1 7.6FXLQ18MVJUFXNQ18MVJU 14.2 10.7 16.1 11.5 18.0 12.2 19.1 12.6 19.3 12.1 19.7 11.4FXLQ24MVJUFXNQ24MVJU 18.9 14.1 21.5 15.1 24.0 15.9 25.5 16.5 25.8 15.8 26.3 14.7ModelIndoor air temp. °FDB (Tc: 115°F (46°C))62 65 68 70 72 75TC TC TC TC TC TCMBH MBH MBH MBH MBH MBHFXLQ07MVJUFXNQ07MVJU 9.9 9.3 8.8 8.5 8.2 7.7FXLQ09MVJUFXNQ09MVJU 12.3 11.5 10.9 10.5 10.1 9.5FXLQ12MVJUFXNQ12MVJU 14.9 14.7 14.0 13.5 13.0 12.3FXLQ18MVJUFXNQ18MVJU 22.3 22.1 21.0 20.0 19.5 18.4FXLQ24MVJUFXNQ24MVJU 29.7 29.5 28.0 27.0 26.0 24.5ModelIndoor air temp. °FWB (Te: 48°F (9°C))61 64 67 70 72 75TC SHF TC SHF TC SHF TC SHF TC SHF TC SHFFXLQ07MVJUFXNQ07MVJU 0.71 1.16 0.77 1.11 0.79 1.09 0.81 1.07 0.84 1.05 0.87 1.03FXLQ09MVJUFXNQ09MVJU 0.71 1.16 0.77 1.11 0.79 1.09 0.81 1.07 0.84 1.05 0.87 1.03FXLQ12MVJUFXNQ12MVJU 0.71 1.16 0.77 1.11 0.79 1.09 0.81 1.07 0.84 1.05 0.87 1.03FXLQ18MVJUFXNQ18MVJU 0.71 1.16 0.77 1.11 0.79 1.09 0.81 1.07 0.84 1.05 0.87 1.03FXLQ24MVJUFXNQ24MVJU 0.71 1.16 0.77 1.10 0.80 1.08 0.81 1.07 0.84 1.05 0.87 1.04Refer to the correction factor table below when a mini-split indoor unit is connected to your VRV system.