• Indoor Units • FLOOR STANDING UNIT • FXLQ-MAVE11• VRV® Systems • Indoor Units41 Specifications1-2 ELECTRICAL SPECIFICATIONS (50HZ) FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVEPower Supply Name VEPhase 1~Frequency Hz 50Voltage V 220-240Current Minimum circuit amps (MCA) A 0.3 0.3 0.6 0.6 0.6 0.6Maximum fuse amps (MFA) A 15Full load amps (FLA) A 0.2 0.2 0.5 0.5 0.5 0.5Voltage range Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminalsis not below or above listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 x FLAMFA is smaller than or equal to 4 x FLANext lower standard fuse rating minimum 15ASelect wire size based on the MCAInstead of a fuse, use a circuit breaker1-3 ELECTRICAL SPECIFICATIONS (60HZ) FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVEPower Supply Name VEPhase 1~Frequency Hz 60Voltage V 220Current Minimum circuit amps (MCA) A 0.3 0.3 0.5 0.5 0.6 0.6Maximum fuse amps (MFA) A 15Full load amps (FLA) A 0.2 0.2 0.4 0.4 0.5 0.5Voltage range Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminalsis not below or above listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 x FLAMFA is smaller than or equal to 4 x FLANext lower standard fuse rating minimum 15ASelect wire size based on the MCAInstead of a fuse, use a circuit breaker