Capacity Tables EDUS391437-F1510 FXUQ-PVJU8. Capacity Tables8.1 Cooling Capacity at Te: 43°F (6°C)TC: Total capacity: MBHSHC: Sensible heat capacity: MBHNotes: 1. These capacity tables can be used when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors suchas the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRVsystem satisfies the required heat load.2. shows rated condition.8.2 Heating CapacityTC: Total capacity: MBHNotes: 1. These capacity tables can be used when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors suchas the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRVsystem satisfies the required heat load.2. shows rated condition.8.3 Correction Factor for Cooling Capacity at Te: 48°F (9°C)TC: Total capacitySHF: Sensible heat factorModel CapacityindicationIndoor air temp. °FWB (Te: 43°F (6°C))61 64 67 70 72 75TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBHFXUQ18PVJU 18 14.2 11.8 16.1 12.9 18.0 13.7 18.4 13.6 18.6 13.0 18.9 12.8FXUQ24PVJU 24 19.0 15.4 21.5 16.9 24.0 18.0 24.5 17.8 24.8 17.0 25.3 16.6FXUQ30PVJU 30 23.7 18.8 26.8 20.7 30.0 22.1 30.6 21.8 31.0 20.9 31.6 20.2FXUQ36PVJU 36 28.4 22.1 32.2 24.2 36.0 26.0 36.7 25.7 37.2 24.7 37.9 23.6Model CapacityindicationIndoor air temp. °FDB62 65 68 70 72 75TC TC TC TC TC TCMBH MBH MBH MBH MBH MBHFXUQ18PVJU 18 23.3 21.9 20.7 20.0 19.3 18.1FXUQ24PVJU 24 31.5 29.5 28.0 27.0 26.0 24.5FXUQ30PVJU 30 39.7 37.1 35.3 34.0 32.7 30.9FXUQ36PVJU 36 46.7 43.7 41.5 40.0 38.5 36.3Model CapacityindicationIndoor air temp. °FWB (Te: 48°F (9°C))61 64 67 70 72 75TC SHF TC SHF TC SHF TC SHF TC SHF TC SHFFXUQ18PVJU 18 0.706 1.162 0.765 1.108 0.786 1.090 0.806 1.073 0.841 1.045 0.865 1.028FXUQ24PVJU 24 0.706 1.162 0.765 1.108 0.786 1.090 0.806 1.073 0.841 1.045 0.865 1.028FXUQ30PVJU 30 0.707 1.161 0.773 1.103 0.795 1.087 0.811 1.077 0.842 1.053 0.865 1.035FXUQ36PVJU 36 0.707 1.161 0.773 1.103 0.795 1.087 0.811 1.077 0.842 1.053 0.865 1.035Refer to the correction factor table below when aresidential indoor unit is connected to your VRV system.