12 EnglishWHEN ELECTRIC WIRING WORK IS NOT FINISHED• Remove the control box lid, connect a power supply (SINGLE PHASE 50Hz 220-240V or 60Hz 220V) toconnections L and N on the power supply terminal block and remote controller to terminal block for remotecontroller. When carrying out wiring work around the control box, make sure none of the connectors comeundone. Be sure to attach the control box lid before turning on the power.Next, press the inspection/test operation button “ ” on the remote controller. The unit will engage thetest operation mode. Press the operation mode selector button “ ” until selecting FAN OPERATION“ ”. Then, press the ON/OFF button “ ”. The indoor unit fan and drain pump will start up. After con-firming drainage (Fig. 23, Fig. 24), turn off the power and remove the power supply. Press “ ” to goback to the first mode.• Note that the fan also starts rotating.• Attach the control box lid as before.Drain pipeService drain outlet (with rubber plug)(Use this outlet to drain water fromthe drain pan)Plastic containerfor pouring(Tube should beabout 100 mm long.) 100[Method of adding water]Fig. 23(mm)REMOTECONTROLTRANSMISSIONWIRINGFORCEDOFFL NSingle phasepower supply50Hz 220-240V60Hz 220VL NL N( ) Power supplyterminal blockFig. 24Controlbox lidRemove the control box lid(take off 2 screws)Remotecontroller wiringTerminal blockfor remote controllerREMOTECONTROL TRANSMISSIONWIRING FORCEDOFF PreviousNext |