Quick Menuwww DaikinApplied com17 OM 1263 • MICROTECH UNIT CONTROLLERQuick MenuItems in the Quick Menu (see Table 2) contain basic unit operating status and control set point parameters The items shown in theQuick Menu are Read Only if a valid password has not been entered The following are brief descriptions of the Quick Menu itemsNo password is required to view the Quick Menu.Table 2: Quick MenuMenu Display Name Default Setting Range Password LevelSystem Mode Local Local/Remote 6Heat/Cool In Heat/Cool Heat/Cool 6CmpIntrLock — Open/Closed 6Dehum Status — Active/Inactive 6Clg Capacity — 0 – 100% NoneOAD/Econo Cap — 0 – 100% NoneHtg Capacity — 0 – 100% NoneReheat Capacity — 0 – 100% NoneSAF Speed — 0 – 100% NoneRF/EF Cap — 0 – 100% NoneOA Temp — -50 0 – 200 0°F NoneSystem Mode is an adjustable item that sets the status forthe for the unit to run on local with field inputs are ignored orremote where operation is based on field inputsHeat/Cool In is an adjustable item that only applicableon heatpump units to determine DX cooling or heatpumpoperationCmpInterLock is an adjustable input safety that can be usedto prevent compressor operation based on external systemsafetiesDehum Status is a status only item which indicates the statusof operation of the dehumidifier. The dehumidifier can be activeor inactiveClg Capacity is a status only item which indicates thepercentage of the unit maximum cooling capacity currentlyoperatingOAD/Econo Cap is a status only item which indicates thepercentage that the outdoor damper or economizer valve iscurrently openHtg Capacity is a status only item which indicates thepercentage of the unit maximum heating capacity currentlyoperatingReheat Capacity is a status only item which indicates thepercentage of the unit maximum reheat capacity currentlyoperatingSAF Capacity is a status only item which indicates thecapacity of the supply air fanRF/EF Capacity is a status only item indicating the capacity ofthe return fan/exhaust air fansOA Temp is a status only item which displays the currenttemperature reading from the unit mounted outdoor airtemperature sensor This sensor is standard on all units