272• Split Sky Air • Outdoor Units 5• Outdoor Units • R-410A • RR-B72 Specifications2-2 ELECTRICAL SPECIFICATIONS RR71B7V3B RR71B7W1B RR100B7V3B RR100B7W1B RR125B7W1BPower Supply Name V3 W1 V3 W1 W1Phase 1 3N 1 3N 3NFrequency Hz 50 50 50 50 50Voltage V 230 400 230 400 400Current Recomended fuses A 32 16 40 16 20Voltage range Minimum V 207 360 207 360 360Maximum V 253 440 253 440 440WiringconnectionsFor Power Supply Quantity 1 1 1 1 1Remark 3 wires (earth wireincluded)5 wires (earth wireincluded)3 wires (earth wireincluded)5 wires (earth wireincluded)5 wires (earth wireincluded)For connectionwith indoorQuantity 1 1 1 1 1Remark 4 wires (earth wire included)Power Supply Intake Outdoor unit onlyNOTES1 Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings ofthis chapter.2 The sound power level is an absolute value indicating the power which a sound source generates.3 Sound values are measured in a semi-anechoic room.4 Heating capacity is only applicable for combination with heat pump outdoor unit.5 In case of drain piping for outdoor unit, drain piping kit (option) is needed.6 Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m,level difference : 0m.7 Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m,level difference : 0m.