4 InstallationInstallation manual10(A)RXP20~35L5V1B + RXF20~35A5V1B + RXF20~25B5V1BR32 split series3P519299-2H – 2019.09NOTICEApplicable legislation on fluorinated greenhouse gasesrequires that the refrigerant charge of the unit is indicatedboth in weight and CO2 equivalent.Formula to calculate the quantity in CO2 equivalenttonnes: GWP value of the refrigerant × total refrigerantcharge [in kg] / 1000Please contact your installer for more information.WARNING: FLAMMABLE MATERIALThe refrigerant inside this unit is mildly flammable.WARNINGThe appliance shall be stored in a room withoutcontinuously operating ignition sources (example: openflames, an operating gas appliance or an operating electricheater).WARNING▪ Do NOT pierce or burn refrigerant cycle parts.▪ Do NOT use cleaning materials or means to acceleratethe defrosting process other than those recommendedby the manufacturer.▪ Be aware that the refrigerant inside the system isodourless.WARNINGThe refrigerant inside the unit is mildly flammable, butnormally does NOT leak. If the refrigerant leaks in theroom and comes in contact with fire from a burner, aheater, or a cooker, this may result in fire, or the formationof a harmful gas.Turn off any combustible heating devices, ventilate theroom, and contact the dealer where you purchased theunit.Do NOT use the unit until a service person confirms thatthe part from which the refrigerant leaked has beenrepaired.4.5.3 To determine the additional refrigerantamountIf the total liquidpiping length is…Then…≤10 m Do NOT add additional refrigerant.>10 m R=(total length (m) of liquidpiping–10 m)×0.020R=Additional charge (kg) (rounded in unitsof 0.01 kg)INFORMATIONPiping length is the one-way length of liquid piping.4.5.4 To determine the complete rechargeamountINFORMATIONIf a complete recharge is necessary, the total refrigerantcharge is: the factory refrigerant charge (see unit nameplate) + the determined additional amount.4.5.5 To charge additional refrigerantWARNING▪ Only use R32 as refrigerant. Other substances maycause explosions and accidents.▪ R32 contains fluorinated greenhouse gases. Its globalwarming potential (GWP) value is 675. Do NOT ventthese gases into the atmosphere.▪ When charging refrigerant, ALWAYS use protectivegloves and safety glasses.Prerequisite: Before charging refrigerant, make sure the refrigerantpiping is connected and checked (leak test and vacuum drying).1 Connect the refrigerant cylinder to the service port.2 Charge the additional refrigerant amount.3 Open the gas stop valve.4.5.6 To fix the fluorinated greenhouse gaseslabel1 Fill in the label as follows:bContains fluorinated greenhouse gases21 1122 kgtCO2 eqGWP × kg1000==+kg=kg=GWP: XXXRXXXaf cdea If a multilingual fluorinated greenhouse gases label isdelivered with the unit (see accessories), peel off theapplicable language and stick it on top of a.b Factory refrigerant charge: see unit name platec Additional refrigerant amount chargedd Total refrigerant chargee Quantity of fluorinated greenhouse gases of the totalrefrigerant charge expressed as tonnes CO2 equivalent.f GWP = Global warming potentialNOTICEApplicable legislation on fluorinated greenhouse gasesrequires that the refrigerant charge of the unit is indicatedboth in weight and CO2 equivalent.Formula to calculate the quantity in CO2 equivalenttonnes: GWP value of the refrigerant × total refrigerantcharge [in kg] / 1000Use the GWP value mentioned on the refrigerant chargelabel. That GWP is based on the current legislation onfluorinated greenhouse gases. The GWP mentioned in themanual might be outdated.2 Fix the label on the inside of the outdoor unit near the gas andliquid stop valves.4.6 Connecting the electrical wiringDANGER: RISK OF ELECTROCUTIONWARNING▪ All wiring MUST be performed by an authorisedelectrician and MUST comply with the applicablelegislation.▪ Make electrical connections to the fixed wiring.▪ All components procured on-site and all electricalconstruction MUST comply with the applicablelegislation.