Outline of Control (Indoor Unit) SiUS39-60270 Function6.2 Thermostat Sensor in Remote ControllerTemperature is controlled by both the thermostat sensor in remote controller and air suctionthermostat in the indoor unit. (This is however limited to when the field setting for the thermostatsensor in remote controller is set to “Use.”)Cooling If there is a significant difference in the preset temperature and the suction temperature, fineadjustment control is carried out using a body thermostat sensor, or using the sensor in theremote controller near the position of the user when the suction temperature is near the presettemperature. Ex: When coolingAssuming the preset temperature in the figure above is 75°F, and the suctiontemperature has changed from 64°F to 86°F (A → F):(This example also assumes there are several other air conditioners, the VRV system is off, andthat temperature changes even when the thermostat sensor is off.)Body thermostat sensor is used for temperatures from 64°F to 73°F (A → C).Remote controller thermostat sensor is used for temperatures from 73°F to 81°F (C → E).Body thermostat sensor is used for temperatures from 81°F to 86°F (E → F).And, assuming suction temperature has changed from 86°F to 64°F (F → A):Body thermostat sensor is used for temperatures from 86°F to 77°F (F → D).Remote controller thermostat sensor is used for temperatures from 77°F to 70°F (D → B).Body thermostat sensor is used for temperatures from 70°F to 64°F (B → A).