SiENBE37-701 SpecificationsSpecifications 331-1 TECHNICAL SPECIFICATIONS FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVENotes Nominal cooling capacities are based on : indoor temperature : 27∞CDB, 19∞CWB, outdoor temperature : 35∞CDB,equivalent refrigerant piping : 7.5m (horizontal)Nominal heating capacities are based on: indoor temperature : 20∞CDB, outdoor temperature : 7∞CDB, 6∞CWB,equivalent refrigerant piping : 7.5m (horizontal)Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.Sound pressure levels are measured at 220V1-2 ELECTRICAL SPECIFICATIONS FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVEPowerSupplyName VEPhase 1 1 1 1Frequency Hz 50 50 50 50Voltage V 220-240Current Minimum circuit amps(MCA) A 0.30 0.30 0.30 0.50Maximum fuse amps(MFA) A 15.00 15.00 15.00 15.00Full load amps (FLA) A 0.20 0.20 0.20 0.40VoltagerangeMinimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below orabove listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 ◊ FLAMFA <= 4 ◊ FLAnext lower standard fuse rating minimum 15Aselect wire size based on the MCAinstead of a fuse, use a circuit breakerFor more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".Finally, click on the document title of your choice.