ELECTRICAL DATARKS+FCQ35BRKS+FCQ50BRKS+FCQ60B* This information was not available at the time of publication.RKS+FHQ35BIndoor unit Outdoor unit Power supply Compressor OFM IFMHz-Volts Voltage range MCA MFA RHz RLA W FLA W FLAFHQ35BUV1B RKS35BVMB 50-230 MAX. 50Hz 253VMIN. 50Hz 207V 15 15 78 4.91 19 0.35 62 0.63D040596RKS+FHQ50BRKS+FHQ60BIndoor unit Outdoor unit Power supply Compressor OFM IFMHz-Volts Voltage range MCA MFA RHz RLA W FLA W FLAFHQ50BUV1B RKS50BVMB 50-230 MAX. 50Hz 253VMIN. 50Hz 207V 18 20 79 7.5 53 0.18 62 0.6FHQ60BUV1B RKS60BVMB 50-230 MAX. 50Hz 253VMIN. 50Hz 207V 18 20 90 8.84 53 0.24 62 0.63D040597RKS+FBQ35BRKS+FBQ50BRKS+FBQ60B* This information was not available at the time of publication.SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load AmpsW : Rated motor output (W)NOTES1. RLA is based on the following conditions:Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.• Pair Application • R-410A • RKS25-35-50-60-71BVMB2 Specifications27• Split - Sky Air • Outdoor Units