EDUS30-900-N REFNET Pipe SystemInstallation of Outdoor Units 53.2 Max. Refrigerant Piping Length3.2.1 Heat Pump System Max. Refrigerant Piping Length (Actual Piping Length) Total Extension lengthTotal Piping length from outside unit to all indoor units 300m Max. Level DifferenceNotes:1. Be sure to use a REFNET Piping Kit for the branch of piping.2. A Branch Part can not be installed to the down flow of the REFNET Header.3. If the outside unit is located under the indoor unit, the level difference is a maximum of 131.2ft.4. For geothermal applications, if the condenser is lower than the indoor units, the maximum vertical separation is 65 ft.First outside Branch ~ Outside units[a] First Branch ~ Indoor Units[c] Outside Units ~ Indoor Units[b+c]Max. RefrigerantPiping Length (ft) 33 ft or less 131ft or less 394 ft or lessOutside Units ~ Indoor Units[H 1 ]Between the Indoor Units[H 2 ]Between the Outside Units[H3 , H 4 ]Max. LevelDifference (ft)164 ft or lessNote 349 ft or less 6.6 ft or less