3 English2. INTRODUCTIONThis installation manual concerns VRV inverters of the DaikinRWEYQ-P series. These units are designed for indoor installation andused for cooling and heatpump applications.The RWEYQ-P units can be combined with Daikin VRV series indoorunits for air conditioning purposes.The present installation manual describes the procedures for unpack-ing, installing and connecting the RWEYQ-P units. Installation of theindoor units is not described in this manual. Always refer to the installa-tion manual supplied with these units for their installation.2-1 CombinationThe indoor units can be installed in the following range.• Always use appropriate indoor units compatible with R410A.To lean which models of indoor units are compatible withR410A, refer to the product catalogs.• Total capacity/quantity of indoor units〈Outside unit〉 〈Total capacity index of indoor units〉 〈Total quantity of indoor units〉RWEYQ72PTJU ................36 ~ 93.5 12 unitsRWEYQ84PTJU ................42 ~ 109 14 unitsRWEYQ144PTJU ..............72 ~ 187 20 unitsRWEYQ168PTJU ..............84 ~ 218 20 unitsRWEYQ216PTJU ............108 ~ 280 22 unitsRWEYQ252PTJU ............126 ~ 327.5 32 units2-2 Standard operation limitThe figures below assume following operating conditions for indoor andoutside units:Equivalent pipe length ......................................................25 ftLevel difference ..................................................................0 ftCooling HeatingA Inlet water temperature (°F)B Indoor temperature (°FWB)C Indoor temperature (°FDB)Range for continuous operationRange for operationRange for pull down operationRange for warming up operation• Operation range of water volume is 13.5~39.5 gpm• The unit is designed for the following operation range:Water temperature: 67~95°FWater volume: 16 gpm or more• During cooling operation when the outside temperature is very low, itis possible that the thermostat switches off automatically in order toprotect the unit from freezing.• Hold ambient temperature at 35~95°FHeat-release from the unit: 0.64 kW / hour (Model 72, 84).It is therefore recommended to always ventilate the room.2-3 Standard supplied accessories• Make sure that the following accessories are included.(Check by removing the front panel.)(Refer to figure 1)1. • Operation manual• Installation manual• Clamp (A)• Clamp (B)• Conduit mounting plate2. Accessory pipes• For discharge gas• For suction gas (1)• For suction gas (2)3. StrainerNOTEThe accessory pipe for discharge gas is used for the heat recovery sys-tem. (Not used for the heat pump system.)2-4 Option accessoryTo install the above outside units, the following optional parts are alsorequired.• Refrigerant branching kit(For R410A only: Always use an appropriate kit dedicated for yoursystem.)〈Heat pump system〉〈Heat recovery system......For 3-tube piping〉〈Heat recovery system......For 2-tube piping〉• Outside unit multi connection piping kit(For R410A only: Always use an appropriate kit dedicated foryour system.)∗ To select an optimum kit, refer to “9. REFRIGERANT PIPING”506070809010011012050607080901001101206050 70 80 90 6050 70 80 90AACBNameAccessory pipesFor dischargegasFor suctiongas (1)For suctiongas (2) Clamp (A) Clamp (B)Quantity 1 pc. 1 pc. 1 pc. 7 pcs. 2 pcs.ShapeName Strainer Conduit mounting plate[Others]• Installation manual• Operation manualQuantity 1 pc. 2 pcs. 2 pcs.ShapeREFNET header KHRP26M22H KHRP26M33H KHRP26M72H KHRP26M73HUREFNET joint KHRP26M22T KHRP26M33T KHRP26M72TU KHRP26M73TUREFNET header KHRP25M33H KHRP25M72H KHRP25M73HUREFNET joint KHRP25M22T KHRP25M33T KHRP25M72TU KHRP25M73TUREFNET header KHRP26M22H KHRP26M33H KHRP26M72H KHRP26M73HUREFNET joint KHRP26M22T KHRP26M33T KHRP26M72TU KHRP26M73TUNumber of outside unitsconnected 2 units 3 unitsHeat pump system BHFP22MA56U BHFP22MA84UHeat recovery system BHFP26MA56U BHFP26MA84U(Note)White Black