■English 8Pump Down OperationIn order to protect the environment, be sure to pump down when relocating or disposing of the unit.1) Remove the valve cap from liquid stop valve and gas stop valve.2) Carry out forced cooling operation.3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.Forced cooling operation■ Using the indoor unit ON/OFF switchPress the indoor unit ON/OFF switch for at least 5 seconds. (Operation will start.)• Forced cooling operation will stop automatically after around 15 minutes.To force a trial operation to stop, press the indoor unit ON/OFF switch.■ Using the indoor unit’s remote controller1) Press “MODE” button and select the cooling mode.2) Press “ON/OFF” button to turn on the system.3) Press both of “TEMP” button and “MODE” button at the same time.4) Press “MODE” button twice. ( will be displayed and the unit will enter trial operation.)• Trial operation will stop automatically after around 30 minutes. To stop trial operation, press “ON/OFF” button.CAUTION• When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.• After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced operation.Gasstop valve Valve capHexagonalwrenchCloseLiquidstop valveService port