ELECTRICAL DATARYS+FTYS20BIndoor unit Outdoor unit Power supply Compressor OFM IFMHz-Volts Voltage range MCA MFA RHz RLA W FLA W FLAFTYS20BVMB RYS20BVMB 50-230 MAX. 50Hz 253VMIN. 50Hz 207V 13.0 15 38 2.91 25 0.35 18 0.203D040467RYS+FTYS25BIndoor unit Outdoor unit Power supply Compressor OFM IFMHz-Volts Voltage range MCA MFA RHz RLA W FLA W FLAFTYS25BVMB RYS25BVMB 50-230 MAX. 50Hz 253VMIN. 50Hz 207V 13.0 15 52 4.01 25 0.35 18 0.203D040468RYS+FTYS35BIndoor unit Outdoor unit Power supply Compressor OFM IFMHz-Volts Voltage range MCA MFA RHz RLA W FLA W FLAFTYS35BVMB RYS35BVMB 50-230 MAX. 50Hz 253VMIN. 50Hz 207V 13.0 15 71 5.51 25 0.35 18 0.203D040469RYS+FTYS50BIndoor unit Outdoor unit Power supply Compressor OFM IFMHz-Volts Voltage range MCA MFA RHz RLA W FLA W FLAFTYS50BVMB RYS50BVMB 50-230 MAX. 50Hz 253VMIN. 50Hz 207V 18 20 72 6.92 53 0.18 40 0.163D040875RYS+FTYS60BIndoor unit Outdoor unit Power supply Compressor OFM IFMHz-Volts Voltage range MCA MFA RHz RLA W FLA W FLAFTYS60BVMB RYS60BVMB 50-230 MAX. 50Hz 253VMIN. 50Hz 207V 18 20 72 8.86 53 0.24 43 0.163D040875SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load AmpsW : Rated motor output (W)NOTES1. RLA is based on the following conditions:Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.• Pair Application • R-410A • RYS20,25,35,50,60BVMB2 Specifications125• Split - Sky Air • Outdoor Units