• Outdoor Units • R-410A • RZQ-DV113• Split Sky Air • Outdoor Units93 Electrical data3D063310SYMBOLSMCA : Min. Circuit Amps (A)TOCA : Total Over Current Amps (A)MFA : Max. Fuse Amps (A) (See note 7)MSC : MSC means the max. current during thestarting of compressor. (A)RLA : Rated Load Amps (A)OFM : Outdoor Fan Motor (A)IFM : Indoor Fan MotorFLA : Full Load AmpskW : Fan Motor Rated Output (kW)RZQ71-140DV1Unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA TOCA MFA MSC RLA kW FLA kW FLANOTES1 RLA is based on the following conditions:Power supply: 50Hz - 230VCoolingIndoor temperature 27°CDB/19°CWBOutdoor temperature 35°CDBHeatingIndoor temperature 20.0°CDBOutdoor temperature 7.0°CDB/6.0°CWB2 TOCA means the total value of each OC set3 Voltage rangeUnits are suitable for use on electrical systems wherevoltage supplied to unit terminals is not below orabove listed operation range limits4 Maximum allowable voltage unbalance betweenphases is 2%5 MCA represents maximum input current., MFArepresents capacity which may accept MCA(next lower standard fuse rating, min.15A)6 Select wire size based on the larger value of MCA orTOCA7 MFA is used to select the circuit breaker and theground fault circuit interrupter (earth leakage circuitbreaker)