• Outdoor Units • R-410A • RZQ100-140B8W1B15• Split Sky Air • Outdoor Units135 Capacity tables5 - 2 Cooling capacity tablesRZQ100B (Pair + Twin / triple)Cooling3TW28121-1AIndoor Outdoor temperature (°C DB)EWB°CEDB°C25 30 35 40TC(kW)SHC(kW)CPI( - )TC(kW)SHC(kW)CPI( - )TC(kW)SHC(kW)CPI( - )TC(kW)SHC(kW)CPI( - )16.0 22 10.2 6.93 0.86 10.2 7.00 1.01 10.5 7.29 1.12 10.1 7.08 1.2318.0 25 11.8 7.59 0.94 11.3 7.45 1.03 11.0 7.27 1.13 10.5 7.06 1.2419.0 27 12.0 7.57 0.95 11.6 7.43 1.03 11.2 7.26 1.13 10.8 7.04 1.2419.5 27 12.1 7.56 0.95 11.8 7.41 1.03 11.3 7.25 1.13 10.9 7.03 1.2422.0 30 12.7 7.46 0.96 12.3 7.32 1.04 11.9 7.16 1.14 11.4 6.96 1.2524.0 32 13.2 7.36 0.96 12.8 7.22 1.05 12.4 7.06 1.15 11.9 6.87 1.27Rated pointCapacity rangeCooling Capacity (kW)CoolingCoefficient of power input ( - )NOTES1 Ratings shown are net capacities which include a deduction for indoor fan motor heat.2 On the figure the mark with show the max, onces at standard conditions.On the figure the mark with show rated capacity and rated coefficient of power input.However the max. Capacity is not guaranteed ecxept at standard condition.3 SHC is based on each EWB and EDB.SHC for other dry bulb temperature = SHC + SHC*.SHC* = SHC correction for other dry bulb.= 0.02 x AFR (m 3/min.) x (1-BF) x (DB*-EDB)Add SHC to SHC*.4 Capacities are based on the following conditions.Outdoor air: 85% RH.However, the condition rated capacity is 7°C DB / 6°C WB. (heating)Corresponding refrigerant piping length : 5.0mLevel difference : 0m5 Coefficient of power input is the percentage when the rated value is defined as 1.00.6 The value contains less than 5% error acording to indoor unit type.7 Air flow rate and (BF) are given in table below:8 Rated power input of each model is tabulated below.(Pair) (Twin)FCQH100D FCQ100C FCQ100D FCQ100B FBQ100B FBQ100C FHQ100 FAQ100 FUQ100 FCQ50Cx2 FCQ50Bx2 FFQ50x2 FBQ50Bx2 FBQ50Cx2 FHQ50x2AFR(BF) 34(0.17) 23.5(0.16) 30(0.11) 28(0.16) 27(0.20) 32(0.14) 24(0.14) 23(0.10) 29(0.07) AFR(BF) 12.5x2(0.21x2) 15x2(0.16x2) 12x2(0.16x2) 14x2(0.15x2) 16x2(0.16x2) 13x2(0.1x2)(Triple)FCQ35Cx3 FCQ35Bx3 FFQ35x3 FBQ35Bx3 FBQ35Cx3 FHQ35x3AFR(BF)10.5x3(0.28x3)14x3(0.16x3)10x3(0.25x3)11.5x3(0.15x3)16x3(0.15x3)13x3(0.2x3)(Pair) (Twin)FCQH100C FCQ100C FCQ100D FCQ100B FBQ100B FBQ100C FHQ100 FAQ100 FUQ100 FCQ50Cx2 FCQ50Bx2 FFQ50x2 FBQ50Cx2 FBQ50x2 FHQ50x2Cooling 2.43 2.64 2.44 2.64 2.86 2.78 3.15 2.78 3.12 Cooling 2.78 2.78 2.79 3.01 2.91 3.32(Triple)FCQ35Cx3 FCQ35Bx3 FFQ35x3 FBQ35x3 FBQ35Cx3 FHQ35x3Cooling 2.78 2.78 2.79 3.01 2.91 3.32SYMBOLSAFR : Air flow rate (m3/min.)BF : Bypass factorEWB : Entering wet bulb temp. (°C WB)EDB : Entering dry bulb temp. (°C DB)TC : Total cooling capacity (kW)SHC : Sensible heat capacity (kW)PI : Power input (Comp.+indoor+outdoor fan motor).CPI : Coefficient of power input ( - )Caution TC and SHC are shown by kW.