313• Split Sky Air • Outdoor Units 6• Outdoor Units • R-410A • RZQ71-140C7V1B3 Electrical data3D059191ASYMBOLSMCA : Min. Circuit Amps (A)TOCA : Total Over Current Amps (A)MFA : Max. Fuse Amps (A) (See note 7)MSC : MSC means the max. current during thestarting of compressor. (A)RLA : Rated Load Amps (A)OFM : Outdoor Fan Motor (A)IFM : Indoor Fan MotorFLA : Full Load AmpskW : Fan Motor Rated Output (kW)NOTES1 RLA is based on the following conditions:Power supply: 50Hz - 230VCoolingIndoor temperature 27°CDB/19°CWBOutdoor temperature 35°CDBHeatingIndoor temperature 20.0°CDBOutdoor temperature 7.0°CDB/6.0°CWB2 TOCA means the total value of each OC set3 Voltage rangeUnits are suitable for use on electrical systems where voltage supplied to unit terminals is not below orabove listed operation range limits4 Maximum allowable voltage unbalance between phases is 2%5 MCA represents maximum input current., MFA represents capacity which may accept MCA(next lower standard fuse rating, min.15A)6 Select wire size based on the larger value of MCA or TOCA7 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)Max. 50Hz 264VMin. 50Hz 198VMax. 50Hz 264VMin. 50Hz 198VRZQ(S)71-100CUnit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA TOCA MFA MSC RLA kW FLA kW FLAMax. 50Hz 264VMin. 50Hz 198V