• Outdoor Unit • Optimized for seasonal efficiency • RZQG-L7V1110• Split - Sky Air ® • Outdoor Unit2810 Wiring diagrams10 - 1 Wiring Diagrams - Single Phase∼∼∼∼∼∼2D074931ARZQ 100-140L7V1A1P : Printed circuit board (Main)A2P : Printed circuit boardA3P : Printed circuit boardA4P : Printed circuit boardA5P : Printed circuit boardBS1∼BS4 : Push button switchC1∼C4 : CapacitorDS1 : Dip switchE1H : Bottomplate heater (Option)F1U,F3U, F4U : Fuse (T 6.3A / 250V)F6U : Fuse (T 5A / 250V)F7U,F8U : Fuse (F 1.0A / 250V)F11U : Fuse (56A / 250V)H1P∼H7P (A2P) : Light emitting diode (service monitor orange)[H2P] Prepare, Test --------- FlickeringMalfunction Detection -- Light upHAP (A1P) : Light emitting diode (service monitor green)K1M : Magnetic contactorK1R : Magnetic relay (Y1S)K4R : Magnetic relay (E1H)(Option)K10R : Magnetic relayL1R : ReactorM1C : Motor (compressor)M1F : Motor (fan)(upper)M2F : Motor (fan)(lower)PS : Switching power supplyQ1DI : Earth leakage circuit breaker(30mA)R1 : ResistorR2 : ResistorR1T : Thermistor (air)R2T : Thermistor (discharge)R3T : Thermistor (Suction)R4T : Thermistor (Heat exchanger)R5T : Thermistor (heat exchanger middle)R6T : Thermistor (liquid)R10T : Thermistor (fin)RC : Signal receiver circuitS1PH : Pressure switch (High)TC : Signal transmission circuitV1R : IGBT Power moduleV2R,V3R : Diode moduleV1T : IGBTX1M : Terminal strip (Power supply)Y1E : Electronic expansion valveY1S : Solenoid valve (4 way valve)Z1C∼Z3C : Noise filter (ferrite core)Z1F∼Z4F : Noise filterOptional connectorX1Y : ConnectorNotes:1. This wiring diagram only applies to the outdoor unit.2. L: Live, N: Neutral, : Field wiring3. : Terminal strip : Connector : Connection: Protective earth (screw) : Relay connector: Noiseless earth : Terminal : Option4. Refer to the combination table and option manual, for connecting wiring to X6A and X28A.5. Refer to the ’’Wiring diagram sticker’’ (on back of front plate) on how to use BS1∼ BS4 and DS1 switch.6. Do not operate the unit by short-circuiting protection device S1PH.7. Colours: WHT=White, RED=Red, BLU=Blue, ORG=Orange,BRN=Brown, GRN=Green, YLW=Yellow, BLK=Black8. Confirm the method of setting the selector switches (DS1) by service manual.Factory setting of all switches: ’’OFF’’.IndoorEl. comp. Assy(Position ofelements)(Front)Position ofcompressorterminal(Back)Outdoor(Note 4)1N∼50Hz220-240VG