36• Split - Sky Air • RZQG-L(8)Y1 21• Outdoor Unit • RZQG-L(8)Y16 Capacity tables6 - 2 Cooling/Heating Capacity TablesRZQG71L9V1RZQG71L8Y1Cooling HeatingSymbolsAFR: Air flow rate [m³/min]BF: Bypass factorEWB: Entering wet-bulb temperature (°C WB)EDB: Entering dry-bulb temperature (°C DB)TC: Maximum total cooling/heating capacity [kW]SHC: Sensible heat capacity [kW]CPI: Coefficient of the power inputPI: Power input [kW]compressor + indoor and outdoor fan motorsCooling HeatingNotes1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.2. = Maximum at standard conditions= Rated capacity and rated coefficient of the power inputThe maximum capacity is not guaranteed except at standard conditions.3. SHC is based on indoor units EWB & EDB.SHC for other dry-bulb temperatures = SHC + SHC*SHC* = SHC correction for other dry-bulb temperatures= 0.02 x AFR (m³/min) x (1-BF) x (DB* - EDB)4. The capacities are based on the following conditions:Outdoor air: 85% RHHowever, the outdoor ambient condition of the rated capacity during heating operation is 7°C DB / 6°C WB.Corresponding refrigerant piping length: 5.0 mLevel difference: 0m5. CPI is a percentage value compared to the rated value which is 1.00.6. The error rate for this value is less than 5% and depends on the indoor unit type.7. The heating performance takes into account the drop that occurs during defrost operation.8. The air flow rate and bypass factor are mentioned in the table. 9. The rated power input for each model is mentioned in the table below.Pair PairFCQHG71F FCQG71F FBQ71C FHQG71C FAQ71C FVQ71C FHQ71CB FUQ71C FBQ71D FCQHG71F FCQG71F FBQ71C FHQG71C FAQ71C FVQ71C FHQ71CB FUQ71C FBQ71DCooling 1,66 2,01 1,94 1,78 2,00 2,02 1,78 1,67 1,89Heating 1,56 1,89 2,05 1,82 2,03 2,06 1,82 1,68 1,87Twin TwinFCQG35F X 2 FBQ35C X 2 FHQ35CB X 2 FFQ35C X 2 FDXS35F X 2 FBQ35D X 2 FNQ35A X 2 FCQG35F X 2 FBQ35C X 2 FHQ35CB X 2 FFQ35C X 2 FDXS35F x 2 FBQ35D X 2 FNQ35A X 2Cooling 2,04 1,98 2,34 2,02 2,23 2,01 2,23Heating 1,92 2,16 2,70 1,88 2,55 2,08 2,5518.0(0.08)20.5(0.13)AFR(BF)21.2( 0.2)21.5(0.14)18.0(0.16)18.0(0.16)20.5(0.13)23.0(0.24)18.0(0.13)15 x 2(0.08 x 2)8,7 x 2(0.17 x 2)AFR(BF)12.5 x 2(0.4 x 2)16 x2(0.15 x 2)14 x 2(0.17 x 2)10 x 2(0.25 x 2)8,7 x 2(0.17 x 2)TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPIԨWB ԨDB kW kW 㸫 kW kW 㸫 kW kW 㸫 kW kW 㸫16,0 22 8,03 5,45 1,00 7,76 5,32 1,11 7,48 5,20 1,21 7,21 5,06 1,3218,0 25 8,40 5,45 1,00 8,11 5,32 1,11 7,83 5,19 1,22 7,54 5,05 1,3319,0 27 8,59 5,44 1,01 8,30 5,32 1,12 8,00 5,18 1,22 7,70 5,05 1,3319,5 27 8,68 5,43 1,01 8,39 5,31 1,12 8,09 5,17 1,22 7,79 5,05 1,3322,0 30 9,15 5,38 1,01 8,84 5,25 1,12 8,52 5,13 1,23 8,21 4,99 1,3424,0 32 9,53 5,31 1,03 9,20 5,19 1,13 8,87 5,06 1,25 8,54 4,92 1,3525 30 35 40Coefficient of the power inputCoefficient of the power inputCooling capacity [kW] Heating capacity [kW]Capacity range Rated point Capacity range Rated pointIndoorOutdoor temperature [°C DB]Indoor3D076748G