• Outdoor Unit • Outdoor units optimized for seasonal efficiency • RZQG-LY112• Split - Sky Air • Outdoor Unit62 SpecificationsFan motor Quantity 1 2Model Brushless DC motorOutput W 94Drive Direct driveSpeed Steps 8Cooling Nom. rpm 670 600 700Superlowrpm -Heating Nom. rpm 560 540Superlowrpm -Sound power level Cooling Nom. dBA 64 66 67 69Sound pressure level Cooling Nom. dBA 48 50 51 52Heating Nom. dBA 50 52 53Night quiet mode Level 1 dBA 43 45Compressor Quantity 1Model 2YC63PXD 2YC90CXDType Hermetically sealed swing compressorOutput W 1,550 2,430 3,100 3,620Starting method Inverter drivenOperation range Cooling Ambient Min. ºCDB -15.0Max. ºCDB 50.0Heating Ambient Min. ºCWB -20.0Max. ºCWB 15.5Refrigerant Type R-410ACharge kg 2.9 4.0Control Expansion valve (electronic type)Circuits Quantity 1Refrigerant oil Type FVC50KCharged volume l 0.9 1.35Piping connections Liquid Quantity 1Type Flare connectionOD mm 9.52Gas Quantity 1Type Flare connectionOD mm 15.9Drain Quantity 5Type HoleID mm -OD mm 26Piping length OU - IU Min. m 5 (2)Max. m 50 75System Equiv-alentm 70 90Charge-lessm 30Additional refrigerant charge kg/m See installation manual 4P302555-1Level difference IU - OU Max. m 30.0IU - IU Max. m 0.5Heat insulation Both liquid and gas pipesDefrost method Pressure equalisingDefrost control Sensor for outdoor heat exchanger temperatureSafety devices Item 01 High pressure switch02 Fan motor thermal protection03 Fuse2-2 Technical Specifications RZQG71LY1 RZQG100LY1 RZQG125LY1 RZQG140LY1