ESIE12-06 Field Setting from Remote ControllerField Setting 1292.3 Settings Contents and Code No. for Indoor UnitsNote: 1. Settings are made simultaneously for the entire group, however, if you select the mode No.inside parentheses, you can also set by each individual unit. Setting changes howevercannot be checked except in the individual mode for those in parentheses. (Even if thesetting are made for the entire group, the display always indicates "01".)2. For FHQG, the second code No. of the "Airflow range setting is set at "03".3. "88" may be displayed to indicate the remote controller is resetting when returning to thenormal mode.2.3.1 Detailed Explanation of Setting ModesFilter Cleaning Sign IntervalWhen "Display" is selected in "Filter cleaning sign" after the unit runs for certain time, "Filtercleaning" will be displayed on the remote controller. This setting is used when the displayinterval of "Filter cleaning" needs to be changed on occasions such as when the filter has beenheavily contaminated.Remote Controller ThermistorSelect the thermistor to control room temperature.The factory setting for the Second Code No. is "02" and room temperature is controlled by theindoor unit suction air thermistor.When the Second Code No. is set to "01", room temperature is controlled by the indoor unitsuction air thermistor and the room temperature thermistor in remote controller as followingfigures.ModeNo.FirstCodeNo.Description of SettingSecond Code No.01 02 03 0410 (20)0 Filter cleaning sign interval Long life filter 2,500 hrs. 1,250 hrs. — —2 Remote controller thermistor Enabled Disabled — —3 Filter cleaning sign Display No display — —11 (21)2 Fan OFF at Thermostat OFF Normal OFF — —3 Airflow rate setting during heating Standard Slightly up Up —4 Automatic operation mode control Available Prohibition — —12 (22)3 Fan speed heating thermostat OFF LL-speed Set-speed — —5 Automatic restart after power failure reset Disabled Enabled — —6 Fan speed cooling thermostat OFF LL-speed Set-speed — —13 (23)0 High air outlet velocity (for high ceilingapplications) Standard Slightly up Up —1 Selection of airflow direction 4-way flow 3-way flow — —4 (2) Airflow range setting Upper Normal Lower —15 (25) 5 Individual setting of ventilation Normal Individualoperation — —Mode No. First CodeNo. SecondCode No. Long Life Filter Setting10 (20) 0 01 2,500 hrs. Contamination Light02 1,250 hrs. Contamination HeavyMode No. First CodeNo. SecondCode No. Thermistor that controls room temperature10 (20) 2 01 Room temperature thermistor in remote controller andindoor unit suction air thermistor02 Indoor unit suction thermistor