• Outdoor Units • R-410A • RZQS71-140C7V1B15• Split Sky Air • Outdoor Units195 Capacity tables5 - 2 Cooling capacity tablesRZQS140C (Pair)CoolingCooling capacityIndoor Outdoor temp. (°CDB)EWB EDB 25 30 35 40(°C) (°C) TC(kW)SHC(kW)CPI(-)TC(kW)SHC(kW)CPI(-)TC(kW)SHC(kW)CPI(-)TC(kW)SHC(kW)CPI(-)16.0 22 12.3 8.29 0.76 12.2 8.37 0.89 12.5 8.73 0.99 12.1 8.46 1.0918.0 25 14.0 9.09 0.83 13.6 8.91 0.91 13.1 8.70 1.00 12.6 8.44 1.1019.0 27 14.4 9.06 0.84 13.9 8.89 0.91 13.4 8.68 1.00 12.8 8.42 1.1019.5 27 14.5 9.05 0.84 14.1 8.87 0.91 13.5 8.66 1.00 13.0 8.41 1.1022.0 30 15.2 8.93 0.85 14.7 8.77 0.92 14.3 8.57 1.01 13.7 8.32 1.1124.0 32 15.8 8.81 0.85 15.3 8.64 0.93 14.8 8.45 1.02 14.3 8.22 1.123TW28149-1SYMBOLSAFR: Air flow rate (m 3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)TC: Total cooling/heating capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)(comp.+indoor+outdoor fan motor)CPI: Coefficient of power input. (-)Caution:TC and SHC are shown by kWNOTES1. Ratings shown are net capacities which include a deduction for indoor fan motor heat2. On the figure the mark j show the max. at standard conditions.On the figure the mark Q show rated capacity and rated coefficient of power input.However the max. capacity is not guaranteed, except at standard condition.3. On the tables Q show rated capacity and rated coefficient of power input.4. SHC is based on each EWB and EDBSHC* = SHC correction for other dry bulbSHC* = 0.02 x AFR (m3 /min.) x (1−BF) x (DB*−EDB)Add SHC* to SHC.5. Capacities are based on following conditions:Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.7. The value contains less than 5% error acording to indoor unit type.8. Heating capacity include the drop of frost formation.9. Air flow rate and BF are tabulated below.(Pair)FBQ140AFR(BF)35(0.14)10. Rated power input of each model is tabulated below.(Pair)Outdoor RZQS140C7Indoor FBQ140B8Cooling 4.97kWHeating 4.99kWCapacity rangeRated pointCooling capacity (kW)Coefficient of power input. (-)