32• Split - Sky Air • RZQSG-L3/9V1 19• Outdoor Unit • RZQSG-L3/9V12 SpecificationsStandard Accessories : Tie-wraps; Quantity : 2;Standard Accessories : Installation manual; Quantity : 1;Operation range Cooling AmbientMin. °CDB -15.0Max. °CDB 46Heating AmbientMin. °CWB -15Max. °CWB 15.5Refrigerant Type R-410ACharge kg 2.75 2.9 4.0TCO 2 eq 5.7 6.1 8.4Control Expansion valve (electronic type)GWP 2,087.5Circuits Quantity 1Piping connections Liquid Quantity 1Type Flare connectionOD mm 9.52Gas Quantity 1Type Flare connectionOD mm 15.9Drain Quantity 3 5Type HoleID mm -OD mm 26Piping length OU - IU Min. m 5Max. m 50System Equivalentm 70Chargelessm 30Additional refrigerant charge kg/m See installation manualLevel difference IU - OU Max. m 15 30.0IU - IU Max. m 0.5Heat insulation Both liquid and gas pipesRefrigerant oil Type FVC50KCharged volume l 0.75 0.9 1.35Defrost method Pressure equalising Reversed cycleDefrost control Sensor for outdoor heat exchanger temperatureSafety devices Item 01 High pressure switch02 Fan motor thermalprotectionLow pressure switch03 Fuse Fan driver overload protector04 - Fuse2-10 Electrical Specifications RZQSG71L3V1 RZQSG100L9V1 RZQSG125L9V1 RZQSG140L9V1Power supply Name V1Phase 1~Frequency Hz 50Voltage V 220-240Voltage range Min. % -10Max. % 10Current - 50Hz Maximum fuse amps (MFA) A 20 -Current Zmax List - Complies to EN61000-3-11Recommended fuses A 25 40Current - 60Hz Maximum fuse amps (MFA) A -Wiring connections For power supply Remark See installation manual outdoor unitFor connection withindoorRemark See installation manual outdoor unitPower supply intake Outdoor unit only2-9 Technical Specifications RZQSG71L3V1 RZQSG100L9V1 RZQSG125L9V1 RZQSG140L9V1