32• Split - Sky Air • RZQSG-L(8)Y1 7• Outdoor Unit • RZQSG-L(8)Y12 SpecificationsNotes(1) PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC(2) See separate drawing for electrical dataPiping connections Liquid Quantity 1Type Flare connectionOD mm 9.52Gas Quantity 1Type Flare connectionOD mm 15.9Drain Quantity 5Type HoleID mm -OD mm 26Piping length OU - IU Min. m 5Max. m 50System Equivalentm 70Chargelessm 30Additional refrigerant charge kg/m See installation manualLevel difference IU - OU Max. m 30IU - IU Max. m 0.5Heat insulation Both liquid and gas pipesDefrost method Reversed cycleDefrost control Sensor for outdoor heat exchanger temperatureSafety devices Item 01 High pressure switch02 Fan driver overload protector03 Fuse2-9 Electrical Specifications RZQSG100L8Y1 RZQSG125L8Y1 RZQSG140LY1Power supply Name Y1Phase 3N~Frequency Hz 50Voltage V 380-415Voltage range Min. % 10Max. % 10Current Zmax List Complies to EN61000-3-11Recommended fuses A 20 25Current - 50Hz Maximum fuse amps (MFA) A 20Current - 60Hz Maximum fuse amps (MFA) A -Wiring connections For power supply Remark See installation manual outdoor unitFor connection withindoorRemark See installation manual outdoor unitPower supply intake Outdoor unit only2-8 Technical Specifications RZQSG100L8Y1 RZQSG125L8Y1 RZQSG140LY1