312• Split - Sky Air • Outdoor Unit 5• Outdoor Unit • Outdoor units optimized for seasonal efficiency • RZQSG-LY12 Specifications2-2 Technical Specifications RZQSG100LY1 RZQSG125LY1 RZQSG140LY1Capacity control Method Inverter controlledCasing Colour Ivory whiteMaterial Painted galvanized steel plateDimensions Unit Height mm 990 1,430Width mm 940Depth mm 320Packed unit Height mm 1,170 1,610Width mm 1,015Depth mm 422Weight Unit kg 82 101Packed unit kg 94 114Heat exchanger Length mm 904Rows Quantity 2Fin pitch mm 1.4Passes Quantity 12 16Face area m² 0.87 1.273Stages Quantity 44 64Empty tubeplateholeQuantity 0Tube type ø7 Hi-XSLFin Type WF finTreatment Anti-corrosion treatment (PE)Fan Type Propeller fanDischarge direction HorizontalQuantity 1 2Air flow rate Cooling Nom. m³/min 76 77 83Superlowm³/min -cfm -Heating Nom. m³/min 83 62Superlowm³/min -cfm -Fan motor Quantity 1 2Model Brushless DC motorOutput W 200 94Drive Direct driveSpeed Steps 8Cooling Nom. rpm 850 855 700Superlowrpm -Heating Nom. rpm 920 540Superlowrpm -Sound power level Cooling Nom. dBA 69 70 69Sound pressure level Cooling Nom. dBA 53 54 53Heating Nom. dBA 57 58 54Night quiet mode Level 1 dBA 49Compressor Quantity 1Model 2YC63PXD 2YC90CXDType Hermetically sealed swing compressorOutput W 2,080 2,620 3,620Starting method Inverter drivenOperation range Cooling Ambient Min. ºCDB -5.0Max. ºCDB 46.0Heating Ambient Min. ºCWB -15.0Max. ºCWB 15.5Refrigerant Type R-410ACharge kg 2.9 4.0Control Expansion valve (electronic type)Circuits Quantity 1