4 CommissioningInstallation manual9AZQS100~140B8V1B + AZQS100~140B7Y1BSplit system air conditioners4P3855281 – 2014.08Connecting to theframeWhen cables are routed from the unit, aprotection sleeve for the conduits (PGinsertions) can be inserted at the knockouthole.When you do not use a wire conduit,protect the wires with vinyl tubes toprevent the edge of the knockout hole fromcutting the wires.a b c d eA BA Inside of the outdoor unitB Outside of the outdoor unita Wireb Bushc Nutd Framee Hose5 Reattach the service cover.6 Connect an earth leakage circuit breaker and fuse to the powersupply line.3.6 Finishing the outdoor unitinstallation3.6.1 To finish the outdoor unit installation1 Insulate and fix the refrigerant piping and interconnection cableas follows:fbaedca Gas pipeb Gas pipe insulationc Interconnection cabled Liquid pipee Liquid pipe insulationf Finishing tape2 Install the service cover.3.6.2 To check the insulation resistance of thecompressorNOTICEIf, after installation, refrigerant accumulates in thecompressor, the insulation resistance over the poles candrop, but if it is at least 1 MΩ, then the unit will not breakdown.▪ Use a 500 V megatester when measuring insulation.▪ Do not use a megatester for lowvoltage circuits.1 Measure the insulation resistance over the poles.If Then≥1 MΩ Insulation resistance is OK. This procedureis finished.<1 MΩ Insulation resistance is not OK. Go to thenext step.2 Turn ON the power and leave it on for 6 hours.Result: The compressor will heat up and evaporate anyrefrigerant in the compressor.3 Measure the insulation resistance again.4 CommissioningNOTICENEVER operate the unit without thermistors and/orpressure sensors/switches. Burning of the compressormight result.4.1 Checklist before test runDo NOT operate the system before the following checks are OK:The indoor units are properly mounted.In case a wireless user interface is used: The indoor unitdecoration panel with infrared receiver is installed.The outdoor unit is properly mounted.The following field wiring has been carried out accordingto this document and the applicable legislation:▪ Between the local supply panel and the outdoor unit▪ Between the outdoor unit and the indoor unitThere are NO missing phases or reversed phases.The system is properly earthed and the earth terminalsare tightened.The fuses or locally installed protection devices areinstalled according to this document, and have not beenbypassed.The power supply voltage matches the voltage on theidentification label of the unit.There are NO loose connections or damaged electricalcomponents in the switch box.The insulation resistance of the compressor is OK.There are NO damaged components or squeezedpipes on the inside of the indoor and outdoor units.There are NO refrigerant leaks.The correct pipe size is installed and the pipes areproperly insulated.The stop valves (gas and liquid) on the outdoor unit arefully open.