Si21-205 FFQ25/35/50/60BV1BRemoval Procedure 2411.9 Removal of Drain PumpProcedure Warning Be sure to wait 10 minutes or more after turning off all power suppliesbefore disassembling work.Step Procedure Points1. Removing the drain pump1 Remove two screwsfixing float switch ass'y.(Screwand)2 Remove the float switchass'y. Remove the float switchbefore removing drain pumpin order to prevent the floatswitch from damage.3 Cut the tie wrap fixingthe drain hose.Remove the screw When pulling out the drainhose, be sure to wear safetygloves to prevent your fingerfrom injury with heatexchanger fin.4 Pull out the drain hose.5 Remove the drainpump.Screw