33• Split - Sky Air • RZAG-MV1 19• Outdoor Unit • RZAG-MV13 Electrical data3 - 1 Electrical DataAZAS-MV1AZAS-MY1RZAG-MV1RZAG-MY1RZASG-MV1RZASG-MY1SymbolsMCA: Minimum Circuit Ampere [A]TOCA: Total overcurrent amps [A]MFA: Maximum Fuse Ampere [A]MSC: Maximum current of the starting compressor [A]RLA: Rated load amps [A]OFM: Outdoor fan motorIFM: Indoor fan motorFLA: Full Load Ampere [A]KW: Fan motor rated output [kW]Notes1. The RLA is based on the following conditions.CoolingIndoor temperature 27.0°C DB / 19.0°C WBOutdoor temperature 35.0°C DBHeatingIndoor temperature 20.0°C DBOutdoor temperature 7.0°C DB / 6.0°C WB2. TOCA is the total value of each overcurrent set.3. Voltage rangeThe units are suitable for use with electrical systems in which the voltage supplied to the unit terminals is not below or above the listed range limits.4. The maximum allowable voltage that is unbalanced between phases is 2%.5. MCA is the maximum input current.The capacity of the MFA must be greater than that of the MCA.Select the MFA according to the table.6. Select the wire size according to the MCA.7. MFA is used to select the circuit breaker and the ground fault circuit interruptor.Earth leakage circuit breaker3D110014ARZAG71-100MV1FCAHG71GVEB RZAG71M7V1B 17,5 㸫 20 㸫 15,5 0,094 0,8 0,091 0,5FCAG35AVEB x2 RZAG71M7V1B 17,6 㸫 20 㸫 15,5 0,094 0,8 0.044 x2 0.3 x2FCAG71AVEB RZAG71M7V1B 17,4 㸫 20 㸫 15,5 0,094 0,8 0,054 0,4FFA35A2VEB x2 RZAG71M7V1B 17,8 㸫 20 㸫 15,5 0,094 0,8 0.050 x2 0.4 x2FBA35A2VEB x2 RZAG71M7V1B 18,2 㸫 20 㸫 15,5 0,094 0,8 0.089 x2 0.6 x2FBA71A2VEB RZAG71M7V1B 17,6 㸫 20 㸫 15,6 0,094 0,8 0,070 0,5FNA35A2VEB x2 RZAG71M7V1B 17,3 㸫 20 㸫 15,5 0,094 0,8 0.034 x2 0,3FUA71AVEB RZAG71M7V1B 17,9 㸫 20 㸫 15,5 0,094 0,8 0,046 0,9FAA71AUVEB RZAG71M7V1B 17,4 㸫 20 㸫 15,5 0,094 0,8 0,048 0,4FVA71AMVEB RZAG71M7V1B 17,6 㸫 20 㸫 15,5 0,094 0,8 0,117 0,6FDXM35F3V1B x2 RZAG71M7V1B 17,6 㸫 20 㸫 15,5 0,094 0,8 0.034 x2 0.3 x2FHA35AVEB x2 RZAG71M7V1B 18,2 㸫 20 㸫 15,5 0,094 0,8 0.060 x2 0.6 x2FHA71AVEB RZAG71M7V1B 17,8 㸫 20 㸫 15,5 0,094 0,8 0,091 0,8FCAHG100GVEB RZAG100M7V1B 27,4 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0,221 1,3FCAG35AVEB x3 RZAG100M7V1B 26,9 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.044 x3 0.3 x3FCAG50AVEB x2 RZAG100M7V1B 26,6 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.039 x2 0.3 x2FCAG100AVEB RZAG100M7V1B 26,7 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0,117 0,7FFA35A2VEB x3 RZAG100M7V1B 27,2 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.050 x3 0.4 x3FFA50A2VEB x2 RZAG100M7V1B 26,8 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.050 x2 0.4 x2FBA35A2VEB x3 RZAG100M7V1B 27,9 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.089 x3 0.6 x3FBA50A2VEB x2 RZAG100M7V1B 27,2 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.089 x2 0.6 x2FBA100A2VEB RZAG100M7V1B 27,0 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0,127 1,0FNA35A2VEB x3 RZAG100M7V1B 26,9 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.034 x3 0.3 x3FNA50A2VEB x2 RZAG100M7V1B 27,0 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.060 x2 0.5 x2FUA100AVEB RZAG100M7V1B 27,4 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0,106 1,3FAA100AUVEB RZAG100M7V1B 26,4 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0,064 0,4FVA100AMVEB RZAG100M7V1B 27,2 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0,238 1,2FDXM35F3V1B x3 RZAG100M7V1B 26,9 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.034 x3 0.3 x3FDXM50F3V1B x2 RZAG100M7V1B 27,0 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.060 x2 0.5 x2FHA35AVEB x3 RZAG100M7V1B 27,9 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.060 x3 0.6 x3FHA50AVEB x2 RZAG100M7V1B 27,2 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0.060 x2 0.6 x2FHA100AVEB RZAG100M7V1B 27,4 㸫 32 㸫 23,5 0.094+0.094 0.75+0.75 0,150 1,3FLACompressor OFM IFMIndoor Outdoor Power supply Voltagerange MCA TOCA MFA MSC RLA kW FLA kW50Hz ~220-240VMinimum: 198 VMaximum 264 V50Hz ~220-240VMinimum: 198 VMaximum 264 V3D110014A