Field Setting of Outdoor Unit SiBE26-70132 Field Setting2. Field Setting of Outdoor Unit2.1 Field Setting from Remote Controller2.1.1 Remote Controller SettingsField setting, which was conventionally done only from outdoor units, can be partly performedfrom a remote controller. The setting procedure is same as that for indoor unit.The table below contains the remote controller settings.: Factory settingsNote 1. Setting in Mode No. 16 is group setting. For individual setting of each outdoor unit, useMode No. 26 and make settings for each indoor unit connected.2. The factory settings for Second Code No. are shown in the boxes with thick lines in the tableabove.3. When returning to Normal Mode, "88" may appear to initialize the remote controller.4. Do not set anything not shown above.2.1.2 Field Setting Procedure1. When in the normal mode, press the “ ” button for a minimum of four seconds, and theFIELD SET MODE is entered.2. Select the desired MODE NO. with the “ ” button (2).3. During group control, when setting by each indoor unit (mode No. 20, 21, 22 and 23 havebeen selected), push the “ ” button (3) and select the INDOOR UNIT NO to be set. (Thisoperation is unnecessary when setting by group.)4. Push the “ ” upper button (4) and select FIRST CODE NO.5. Push the “ ” lower button (5) and select the SECOND CODE NO.6. Push the “ ” button (6) once and the present settings are SET.7. Push the “ ” button (7) to return to the NORMAL MODE.Mode No. Firstcode Description Second No.01 02 03 04 05 06 0716 or 26 0 Select from “Low NightNoise Setting”,“Capacity PrecedenceSetting”.Disabled(Factorysetting)Automaticlow noiseactivationLow NightNoisesetting +Capacityprecedencesetting— — — —1 Setting of “startingtime”, and “ending time”for the Low Night NoiseSetting.22h00~06h0022h00~08h0022h00 ~06h0022h00 ~08h00(Factorysetting)20h00 ~08h0022h00~08h0020h00 ~08h002 Selection of FlatInstallation Disabled(Factorysetting)— — — Flatinstallationapplicable— —3 Standard(Factorysetting)DelayeddefroststartEarlydefroststart— — — —