Si-95 Test OperationTest Operation Inverter K Series 491.3.3 Monitor Mode After making sure the data is correct, push the RETURN button and return to No. 0, or push the MODEbutton and return to setting mode 1.16 432 8 21MODE TEST L.N.O.P. SEQ.HWL STARTH1P H2P H3P H4P H5P H6P H7PMODETo enter the monitor mode, push the MODE button when in setting mode 1.RETURNSETSETSETThe lower 4 digits indicate the setting in each of the framesbelow.The No. 1 cool/heat group address is expressed as abinary number consisting of the lower 6 digits. (0 - 63)In (1), the address is 010110 (binary number), whichtranslates to 16 + 4 + 2 = 22 (base 10 number). In otherwords, the address is 22.Tc (high pressure for heating) HighNormal (factory set)LowTe (low pressure for cooling) HighNormal (factory set)LowDefrost(temperature setting for defrost)Quick defrostNormal (factory set)Slow defrostEMG(emergency operation whenmalfunction occurs)ONOFPush the SET button and match with the LEDs No. 1 - 15, push the RETURN button,and enter the data for each setting.* Data such as addresses and number of units is expressed as binary numbers; the twoways of expressing are as follows:∗ See the following page for a list of the data for No. 1 - 16.1The number of terminal blocks for No. 12 and 13 isexpressed as an 8-digit binary number which is thecombination of four upper and four lower digits for No.12 and 13 respectively. (0 - 128)In (2), the address for No. 12 is 0101, the address forNo. 13 is 0110, and the combination of the two is01010110 (binary number), which translates to 64 + 16+ 4 + 2 = 86 (base 10 number). In other words, thenumber of terminal blocks is 86.64 16No12 128 3224 1No13 8 2No 0RETURNNo 1No 16RETURN(1 to 15 times)(VF018)SI-95.BOOK Page 49 Friday, March 31, 2000 10:59 AM