• Indoor Units • 4-WAY BLOW CEILING SUSPENDED CASSETTE • BEVQ-MAVE• VRV Systems • Indoor Units1411 Junction box - BEVQ-MAVE11 - 1 SpecificationsIndoorUnit VRVSystems BEVQ-MAVE 4-WayBlow11-1-1Technical Specifications BEVQ71MAVE BEVQ100MAVE BEVQ125MAVEPower input(Nominal)Cooling kW 0.189 0.298 0.298Heating kW 0.169 0.278 0.278Casing Material Galvanised steel plateDimensions Packing Height mm 100 100 100Width mm 350 350 350Depth mm 225 225 225Sound absorbing thermal insulation material Flame and heat resistant foamed polyethereneWeight Unit kg 3.0 3.0 3.5Indoor Units Liquid (OD) Type Flare connectionDiameter mm 9.5 9.5 9.5Gas Type Flare connectionDiameter mm 15.9 15.9 15.9Outdoor Unit Liquid (OD) Type Flare connectionDiameter mm 9.5 9.5 9.5Suction gas(OD)Type Flare connectionDiameter mm 15.9 15.9 15.9StandardAccessoriesItem Installation manualGas piping connectionsInsulation for fittingSealing materialClamps11-1-2Electrical Specifications BEVQ71MAVE BEVQ100MAVE BEVQ125MAVEPower Supply Name VEPhase 1˜Frequency Hz 50/60Voltage V 220-240Voltage range Minimum V -10%Maximum V +10%Total circuit Minimum circuit amps(MCA)A 0.8 1.3 1.3Maximum fuse amps (MFA) A 15 15 15Notes Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminals is not belowor above listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA: MCA=1.25 X FLASelect wire size based on MCAInstead of a fuse, use a circuit breakerMFA is smaller than or equal to 4 x FLANext lower standard fuse rating minimum 15A