• BS Units • BS UNITS • BSVQ100-250P8B• VRV ® Systems • BS Units44 Dimensional drawing & centre of gravity4 - 1 Dimensional drawingBSVQ250PV13D056012AN OTES1 Electric box can also be fixed on the other side of the unit.2 Be sure to install a inspection door at electric box side.3 Attached pipe (1) and attached pipe (2) is used in case ofconnecting with indoor capacity index more than 160 and lessthan 200 In case of connecting one indoor unit of 200 type, onlygas pipe connection port need Attached pipe (1).4 Small sound will be made when changing over the motoroperated valve, which may be disturbing. Do not install it at theplace such as bedroom under roof.Nr Name Description1 Suction gas pipe connection port ø22.2mm brazing connection2 HP/LP gas pipe connection port ø19.1mm brazing connection3 Liquid pipe connection port ø9.5mm brazing connection4 Gas pipe connection port ø22.2mm brazing connection5 Liquid pipe connection port ø9.5mm brazing connection6 Electric box (note 1.)7 Suspension brackets M8 ~M108 Grounding terminal M49 Attached pipe (1) (Note. 3) ø19.1mm brazing connection10 Attached pipe (2) (Note. 3) ø15.9mm brazing connection(Suspension bolt pitch)300 or more(Suspension bolt pitch)(Servicing space)Servicing spaceInspection door(Note 2.)Location of unit’s name plate - - - right side of electric box300 or more(Servicing space)65ormore(Servicingspace)400 or more(Servicing space)400 or more(Servicing space)(In case of use Attached pipe)(Servicing space)50ormore(Servicingspace)(Note 1.)BSVQ160PV13D058004N OTES1 Electric box can also be fixed on the other side of the unit.2 Be sure to install an inspection door at electric box side.3 Attached pipe is only used in case of connecting with indoor unitcapacity index 150 or more and 160 or less.4 Small sound of refrigerant will be made, which may bedisturbing.Do not install it at the place such as bedroom under roof.Nr Name Description1 Suction gas pipe connection port ø15.9mm brazing connection2 HP/LP gas pipe connection port ø12.7mm brazing connection3 Liquid pipe connection port ø9.5mm brazing connection4 Gas pipe connection port ø15.9mm brazing connection5 Liquid pipe connection port ø9.5mm brazing connection6 Electric box (note 1.)7 Suspension brackets M8 ~M108 Grounding terminal M49 Attached pipe (1) (Note. 3) ø19.1mm brazing connection10 Attached pipe (2) (Note. 3) ø15.9mm brazing connection(Suspension bolt pitch)250 or more(Suspension bolt pitch)(Servicing space)Servicing spaceInspection door(Note 2.)Location of unit’s name plate - - - right side of electric box250 or more(Servicing space)65ormore(Servicingspace)350 or more(Servicing space)350 or more(Servicing space)(In case of use Attached pipe)(Suspension bolt pitch)50ormore(Servicingspace)(Note 1.)