Installation Guide ECL Comfort 210 / 310, application A2605.8 ApplicationThe section "Application" describes specific application relatedissues.Parameters indicated with an ID no. like "1x607" mean a universalparameter.x stands for circuit / parameter group.MENU > Settings > ApplicationECA addr. (ECA address, choice of Remote Control Unit) 1x010Circuit Setting range Factory settingAll * *DecidestheroomtemperaturesignaltransferandcommunicationwiththeRemote Control Unit.* See Appendix “Parameter ID overview”OFF: No Remote Control Unit. Only room temperature sensor,if any.A: Remote Control Unit ECA 30 / 31 with address A.B: Remote Control Unit ECA 30 / 31 with address B.The Remote Control Unit must be set accordingly (A or B).MENU > Settings > ApplicationDemand offset 1x017Circuit Setting range Factory settingAll * *Thedesiredflowtemperatureinheatingcircuit1canbeinfluencedbythedemandforadesiredflowtemperaturefromanothercontroller(slave)oranother circuit.* See Appendix “Parameter ID overview”OFF: The desired flow temperature in circuit 1 is notinfluenced by the demand of any other controller (slaveor circuit 2).Value: The desired flow temperature is increased by the setvalue in ‘Demand offset’, if the demand of the slave /circuit 2 is higher.Temp. Setting in‘Demandoffset’Des. flowtemp.,circuit 1Des. flowtemp.,circuit 2TimeThe function of ‘Demand offset’ can compensate for heat lossesbetween master and slave controlled systems.When setting "Demand offset" to a value, the return temperaturelimitation will react according to the highest limitation value (Heating/ DHW).Danfoss District Energy VI.LG.F2.02 DEN-SMT/DK 73