Installation Guide ECL Comfort 210 / 310, application A231 / A3314.0 Settings overviewIt is recommendable to make a note of any changed settings in the empty columns.Setting ID Page Factory settings in circuit(s)1 2 3Heat curve 55Temp. max. (flow temp. limit, max.) — A231.1 / A331.1 11178 56 90 °CTemp. min. (flow temp. limit, min.) 11177 56 10 °CHeat curve 57Temp. max. (flow temp. limit, max.) — A231.2 / A331.2 58Temp. min. (flow temp. limit, min.) 11177 58 10 °CHigh supp. T X2 (high value of supply temp.) — A231.2 / A331.2 11300 58 150 °CHigh T max Y2 (high value of max limitation) — A231.2 / A331.2 11301 58 95 °CLow supply T X1(low value of supply temp.) — A231.2 / A331.2 11302 59 70 °CLow T max Y1 (low value of max limitation) — A231.2 / A331.2 11303 59 50 °CHigh T out X1 (return temp. limitation, high limit, X-axis) 11031 60 15 °CLow limit Y1 (return temp. limitation, low limit, Y-axis) 11032 60 40 °CLow T out X2 (return temp. limitation, low limit, X-axis) 11033 60 -15 °CHigh limit Y2 (return temp. limitation, high limit, Y-axis) 11034 61 60 °CInfl. - max. (return temp. limitation - max. influence) 11035 61 0.0Infl. - min. (return temp. limitation - min. influence) 11036 61 0.0Adapt. time (adaptation time) 11037 61 25 sPriority (priority for return temp. limitation) 11085 62 OFFHigh T out X1 (flow / power limitation, high limit, X-axis) 11119 63 15 °CLow limit Y1 (flow / power limitation, low limit, Y-axis) 11117 64 999.9l/hLow T out X2 (flow / power limitation, low limit, X-axis) 11118 64 -15 °CHigh limit Y2 (flow / power limitation, high limit, Y-axis) 11116 64 999.9l/hAdapt. time (adaptation time) 11112 64 OFFFilter constant 11113 64 10Input type, A231 11109 65 OFFInput type — A331 11109 65 OFFUnits — A231 11115 65 l/hUnits — A331 11115 65 l/hAuto saving (saving temp. dependent on outdoor temp.) 11011 66 -15 °CBoost 11012 66 OFFRamp (reference ramping) 11013 67 OFFOptimizer (optimizing time constant) 11014 67 OFFPre-stop (optimized stop time) 11026 68 ONTotal stop 11021 68 OFFCut-out (limit for heating cut-out) 11179 69 20 °CMotor pr. (motor protection) 11174 70 OFFXp (proportional band) 11184 70 80 KTn (integration time constant) 11185 70 30 sM run (running time of the motorized control valve) 11186 70 50 sNz (neutral zone) 11187 71 3 KChan.-over time (change-over time) 11314 72 5 sDanfoss District Energy VI.LG.P1.02 DEN-SMT/DK 53