Instructions ECL Comfort 210 / 310, communication descriptionTable 6-7:Setting Value Address (if DHW is circuit 2)Day 0-127 12122Start time 0-47 12123Duration [m] 10-600 12124Desired temperature [°C] 9-110 12125 The anti-bacteria function is not active if the frostprotection mode is active.6.9 HolidayThe address range for holiday settings is from 10700 to 10839.Table 6-8 shows how a schedule consists of a mode (modefrom Table 6-9 depending on application), a start time (day-month-year) and an end time (day-month-year) as well as theaddresses to change them. Up to 20 schedules can be definedbut typically less will actually be used depending on theapplication. See the application instructions for informationabout which holiday schedules belong to the specific circuits.Table 6-8: Addresses for holiday schedulesMode Start day StartmonthStart year End day End month End yearSchedule P1 10700 10701 10702 10703 10704 10705 10706Schedule P2 10707 10708 10709 10710 10711 10712 10713Schedule P3 10714 10715 10716 10717 10718 10719 10720Schedule P4 10721 10722 10723 10724 10725 10726 10727… … … … … … … …Schedule P20 10833 10834 10835 10836 10837 10838 10839Maximum start or end year is 2050.Table 6-9: Modes for holiday schedulesOperating mode Code Display symbolScheduled operation (holiday off) 0Constant comfort temperature 17 – 23h Comfort temperature 2Constant setback temperature 3Frost protection / standby 4 /Danfoss District Energy VI.LG.V3.02 DEN-SMT/DK 16