Operating Guide ECL Comfort 210 / 310, application A247 / A3475.10 Tank temperatureParameters indicated with an ID no. like "1x607" mean a universalparameter.x stands for circuit / parameter group.MENU > Settings > Tank temperatureFlow T adapt time (Flow temperature, adaptation time) 1x068Circuit Setting range Factory settingAll * *Set the adaptation time (in seconds) for the desired temperature in theprimarycircuit,basedonthedesiredchargingtemperature.TheECLComfortcontrollergraduallyincreasesthedesiredflowtemperatureintheprimarycircuitinordertomaintainthedesiredchargingtemperature.* See Appendix “Parameter ID overview”OFF: The desired flow temperature in the primary circuit isnot adapted to the desired charging temperature.Lowvalue:The adaptation is quick.Highvalue:The adaptation is slow.The desired heating / charging temperature cannot be higher than theset temperature in 'Max. charge T’.MENU > Settings > Tank temperatureMax. chargeT(maximumheating/chargingtemperature) 1x152Circuit Setting range Factory settingAll * *Setthemax. heating/chargingtemperaturefortheDHW.Value: Set the temperature.* See Appendix “Parameter ID overview”NOTE:The desired DHW temperature will be reduced if "Max. charge T" islower than (Desired DHW temp. + Charge difference).Example:Desired DHW temp. = 50 °CCharge difference = 10 KMax. charge T = 55 °CResult:Desired DHW temp. will be reduced to 45 °C.Danfoss District Energy VI.LG.S3.02 DEN-SMT/DK 105