7.7 Parameter ID overviewA232.x or A332.x — x refers to the subtypes listed in the column.ID Parameter Name A232.x A332.x Setting range Factory UnitOwnsettings11003 Circuit, sensor 3 OFF ; ON ON11010 ECA addr. 1 1, 2, 4 OFF ; A ; B A 99-||- 3 OFF ; A ; B OFF11011 Auto saving 1 1, 2, 3, 4 OFF, -29 ... 10 OFF °C 8611012 Boost 1 1, 2, 3, 4 OFF, 1 ... 99 OFF % 8711014 Optimizer 1 1, 2, 3, 4 OFF, 10 ... 59 OFF 8811015 Adapt. time 1 1, 2, 3, 4 OFF, 1 ... 50 OFF Sec 7311020 Based on 1 1, 2, 3, 4 OUT ; ROOM OUT 8911021 Total stop 1 1, 2, 3, 4 OFF ; ON OFF 8911022 P exercise 1 1, 2, 3, 4 OFF ; ON OFF 9911023 M exercise 1 1, 2, 3, 4 OFF ; ON OFF 9911024 Actuator 1 1, 2, 3, 4 ABV ; GEAR GEAR 9311026 Pre-stop 1 1, 2, 3, 4 OFF ; ON ON 9011031 High T out X1 1, 2, 3, 4 -60 ... 20 15 °C 8011032 Low limit Y1 1, 2, 3, 4 10 ... 150 40 °C 8011033 Low T out X2 1, 2, 3, 4 -60 ... 20 -15 °C 8011034 High limit Y2 1, 2, 3, 4 10 ... 150 60 °C 8011035 Infl. - max. 1, 2, 3, 4 -9.9 ... 9.9 0.0 8111036 Infl. - min. 1, 2, 3, 4 -9.9 ... 9.9 0.0 8111037 Adapt. time 1, 2, 3, 4 OFF, 1 ... 50 25 Sec 8111038 Stop at T out 1 1, 2, 3, 4 -20 ... 50 10 °C 10911040 P post-run 1 1, 2, 3, 4 0 ... 99 3 Min 10011060 Limit 1 1, 2, 3, 4 1 ... 80 25 °C 8411061 Adapt. time 1 1, 2, 3, 4 OFF, 1 ... 50 OFF Sec 8411062 Infl. - max. 1 1, 2, 3, 4 -9.9 ... 0.0 0.0 8411077 P frost T 1 1, 2, 4 OFF, -10 ... 20 2 °C 100-||- 3 OFF, -10 ... 20 OFF °C11078 P heat T 1 1, 2, 3, 4 5 ... 110 20 °C 10111079 Max. flow T 1 1, 2, 3, 4 10 ... 110 100 °C 11311080 Delay 1 1, 2, 3, 4 5 ... 250 30 Sec 11411083 Add. function 1, 2, 3, 4 3 ... 6 6 10911089 Acc. output func. 1 0 ... 6 0 110-||- 1, 2, 3, 4 0 ... 2 011093 Frost pr. T 1 1, 2, 3, 4 5 ... 40 10 °C 10111141 Ext. input 1 OFF;S1;S2;S3;S4; S5 ; S6 ; S7 ; S8S8 101-||- 1, 4 OFF ; S1 ; S2 ; S3 ;S4 ; S5 ; S6 ; S7 ; S8; S9 ; S10S8156 | © Danfoss | 2017.08 VI.JM.G2.02Operating Guide ECL Comfort 210/296/310, application A232 / A332