7.7 Parameter ID overviewA267.x — x refers to the subtypes listed in the column.ID Parameter Name A267.x Setting range Factory Unit Own settings10512 Prog. execution 1 OFF ; ON OFF10514 Max. pwr. failure 1 5 ... 3000 30 Min10903 Ramp X5-X6 1 OFF, 1 ... 20 510904 Ramp X7-X8 1 OFF, 1 ... 20 510912 Appl. continue 1 OFF ; ON OFF10913 After power fail. 1 STOP ; START OFF10930 X1 1 0 ... 1200 0 h10931 X2 1 0 ... 1200 0 h10932 X3 1 0 ... 1200 0 h10933 X4 1 0 ... 1200 0 h10934 X5 1 0 ... 1200 0 h10935 X6 1 0 ... 1200 360 h10936 X7 1 0 ... 1200 720 h10937 X8 1 0 ... 1200 1080 h11004 Desired T 1 5 ... 150 50 °C 5011010 ECA addr. 1 OFF ; A ; B OFF 7111011 Auto saving 1 OFF, -29 ... 10 -15 °C 6011012 Boost 1 OFF, 1 ... 99 OFF % 6111013 Ramp 1 OFF, 1 ... 99 OFF Min 6211014 Optimizer 1 OFF, 10 ... 59 OFF 6211015 Adapt. time 1 OFF, 1 ... 50 OFF Sec 5211017 Demand offset 1 OFF, 1 ... 20 OFF K 7111020 Based on 1 OUT ; ROOM OUT 6311021 Total stop 1 OFF ; ON OFF 6311022 P exercise 1 OFF ; ON ON 7111023 M exercise 1 OFF ; ON OFF 7211024 Actuator 1 ABV ; GEAR GEAR 6811026 Pre-stop 1 OFF ; ON ON 6411028 Con. T, ret. T lim. 1 10 ... 110 70 °C 5611031 High T out X1 1 -60 ... 20 15 °C 5711032 Low limit Y1 1 10 ... 150 50 °C 5711033 Low T out X2 1 -60 ... 20 -15 °C 5711034 High limit Y2 1 10 ... 150 60 °C 5811035 Infl. - max. 1 -9.9 ... 9.9 -2.0 5811036 Infl. - min. 1 -9.9 ... 9.9 0.0 5811037 Adapt. time 1 OFF, 1 ... 50 25 Sec 5811040 P post-run 1 0 ... 99 3 Min 7211043 Parallel operation 1 OFF, 1 ... 99, ON OFF K 64126 | © Danfoss | 2018.01 VI.GU.G2.02Operating Guide ECL Comfort 210 / 296, application A267