Operating Guide ECL Comfort 310, application P3186.4 Tank temperatureMENU > Event > Charge TMENU > Event > Tank temperatureMENU > Event > DHW flow TMENU > Event > Supply TUpper difference 1x147Circuit Setting range Factory settingAll * *Theeventisregisteredifthetemperatureinquestionincreasesmorethanthe set difference (acceptable temperature difference above the desiredtemperature). See also 'Delay'.* See Appendix “Parameter ID overview”OFF: The event function is not active.Value: The event function is active if the actual temperaturegets above the acceptable difference.Upperdifference87H1698.10Da nfos sXY# 1 ## 2 #X = TimeY = Temperature#1# = Upper difference#2# = Desired temperatureMENU > Event > Tank temperatureEvent priority 42 9042Circuit Setting range Factory settingAll * *Theeventnumberandprioritypossibilities.TheeventcanbeactivatedifthetanktemperatureS6hasbeentoohighfor more than the set "Delay" time.* See Appendix “Parameter ID overview”0: Log of event not active1: Log of event in list2: Log of event in list and notice (letter symbol in display)3: Log of event in list and alarm (bell symbol in display andactivation of alarm output)MENU > Event > Charge TMENU > Event > Tank temperatureMENU > Event > DHW flow TLower difference 1x148Circuit Setting range Factory settingAll * *Theeventisregisteredifthetemperatureinquestiondecreasesmorethanthe set difference (acceptable temperature difference below the desiredtemperature). See also 'Delay'.* See Appendix “Parameter ID overview”OFF: The event function is not active.Value: The event function is active if the actual temperaturegets below the acceptable difference.Lowerdifference87H1697.10Da nfos sXY# 1 ## 2 #X = TimeY = Temperature#1# = Lower difference#2# = Desired temperatureDanfoss District Energy VI.JM.Q3.02 DEN-SMT/DK 87