8.1.2 Line Power Supply 3x380–480 V ACType Designation P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5Typical Shaft Output [kW] 1.1 1.5 2.2 3.0 4.0 5.5 7.5Typical Shaft Output [HP] at 460 V 1.5 2.0 2.9 4.0 5.0 7.5 10IP20/Chassis6) A2 A2 A2 A2 A2 A3 A3IP55/Type 12 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A5 A5IP66/NEMA 4X A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A5 A5Output currentContinuous (3x380–440 V) [A] 3 4.1 5.6 7.2 10 13 16Intermittent (3x380–440 V) [A] 3.3 4.5 6.2 7.9 11 14.3 17.6Continuous (3x441–480 V) [A] 2.7 3.4 4.8 6.3 8.2 11 14.5Intermittent (3x441–480 V) [A] 3.0 3.7 5.3 6.9 9.0 12.1 15.4Continuous kVA (400 V AC) [kVA] 2.1 2.8 3.9 5.0 6.9 9.0 11.0Continuous kVA (460 V AC) [kVA] 2.4 2.7 3.8 5.0 6.5 8.8 11.6Max. input currentContinuous (3x380–440 V) [A] 2.7 3.7 5.0 6.5 9.0 11.7 14.4Intermittent (3x380–440 V) [A] 3.0 4.1 5.5 7.2 9.9 12.9 15.8Continuous (3x441–480 V) [A] 2.7 3.1 4.3 5.7 7.4 9.9 13.0Intermittent (3x441–480 V) [A] 3.0 3.4 4.7 6.3 8.1 10.9 14.3Additional specificationsEstimated power lossat rated max. load [W]4) 58 62 88 116 124 187 255IP20, IP21 max. cable cross-section(line power, motor, brake and loadsharing) [mm2/(AWG)]2)4, 4, 4 (12, 12, 12)(min. 0.2 (24))IP55, IP66 max. cable cross-section(line power, motor, brake and loadsharing) [mm2/(AWG)]2)4, 4, 4 (12, 12, 12)Max. cable cross-section withdisconnect 6, 4, 4 (10, 12, 12)Efficiency3) 0.96 0.97 0.97 0.97 0.97 0.97 0.97Table 8.3 Line Power Supply 3x380–480 V AC - Normal overload 110% for 1 minute, P1K1-P7K5Specifications Instruction Manual50 Danfoss A/S © Rev. 2014-04-10 All rights reserved. MG16E32288